KNX Gateway: supported parameters and datatypes (DPT)
Parameters of the Ilevia Manager KNX gateway (X1 Plus or KNX/IP interface, KNX Secure) and all 453 supported KNX datatypes, with the components created for each one.
The Knx3 gateway is Ilevia Manager's next-generation KNX connection: it connects to the KNX bus directly from X1 Plus or via a KNX/IP interface, supports KNX Secure and recognizes 453 data types (DPT). For each DPT, Manager already knows which components to create, so a group object becomes a ready-to-use component in just a few clicks.
In short: 453 supported DPTs in 102 main types · KNX Secure with ETS keyring file · components automatically created from the DPT with the KNX Datapoint component.
Gateway parameters
Open Gateways, create a gateway (see Adding and removing a gateway) and choose Knx3 under Protocol.
Field | Initial value | Meaning |
|---|---|---|
Type | X1 plus | X1 plus: uses the built-in KNX connection of X1 Plus, with no additional data. Custom: uses an external KNX/IP interface and shows the Ip Address and Port fields. |
Ip Address | 127.0.0.1 | Only with Type = Custom: IP address of the KNX/IP interface. |
Port | 3671 | Only with Type = Custom: port of the KNX/IP interface (3671 is the standard KNXnet/IP port). |
KNX Individual Address | 15.15.240 | Required. Physical address used by the Ilevia server on the KNX bus. Use a free address from the ETS project; if the field is empty, it is highlighted in red. |
Secure | off | Enables KNX Secure communication. It turns on automatically when you load a keyring file. |
KNX Secure Keyring | no file | .knxkeys file exported from ETS. Click Choose File or drag the file onto the box: it is saved in the project and the text Keyring loaded appears. |
Keyring Password | — | The password chosen in ETS when you exported the keyring. Manager checks it against the file: if it does not match, the field turns red. |
The keyring file and its password provide access to the plant's secure communication: keep them confidential and update the keyring in Manager every time you re-export it from ETS.
KNX component parameters
In components connected to a Knx3 gateway, the KNX section contains these common fields:
Field | Meaning |
|---|---|
Write address | Group address to which the component sends commands. |
Feedback address | Group address from which the component reads the status (the actual actuator status). |
Virtual feedback | If no status address exists, the component updates its own status with the value it sent. |
Read bus value on startup | At startup, the server reads the current value from the bus, so the interface starts already updated. |
Invert value | (Switch) Inverts the value: 1 becomes 0 and vice versa. |
Group addresses have three levels (main/middle/sub, e.g. 1/2/3). Next to each address, a small menu lets you enable periodic sending (Send Interval, for write addresses) or periodic reading (Read Interval, for status addresses), with an interval in seconds: initial value 30 s, disabled.
Main component addresses
Some components have one address for each function, each with its own DPT:
Component | Functions and DPT |
|---|---|
Switch | Command and status (DPT 1.001) |
Pulse | Pulse (DPT 1.001) |
Dimmer | On/Off (1.001) · Relative dimming (3.007) · Absolute dimming (5.001) |
White light | On/Off (1.001) · Dimming (5.001) · Relative dimming (3.007) · Color temperature (7.600) |
RGB light | On/Off (1.001) · White (5.001) · Dimming (5.001) · Relative dimming (3.007) · Color: RGB (3× 5.001), RGBW (4× 5.001), combined RGB (232.600), combined RGBW (251.600), HSV (5.003 + 2× 5.001), HSVW (5.003 + 3× 5.001) |
Shutter | Up/Down (1.008, with Invert movement) · Position (5.001) |
Thermostat | Setpoint (9.001) · Absolute offset (9.002) · Relative offset (6.010) |
Climate thermostat | Setpoint (9.001) · Control mode (20.105) · Ventilation (5.001) · Heating/Cooling (1.100) · On/Off (1.001) · Humidity (9.007, status only) |
Scenario | Scene control (18.001): scene number 0–63 and the Store current state into the scene (learn) option to save the scene |
The KNX Datapoint component
For any other group object, use the KNX Datapoint component:
Enter Write address and/or Feedback address.
Choose the DPT from the list: you can search by number or by name (e.g. 9.001 - Value Temp).
The Parameters table shows the DPT fields and the component that Manager will use for each one.
Press Create components: Manager creates and links the components (Switch, Slider, Info, Thermostat…). Fields that are already linked are not duplicated.
Supported datatypes (DPT)
The Knx3 gateway recognizes 453 DPTs. The DPT number has two parts: the main type (before the dot) says how the value is represented on the bus (1 bit, 1 byte, floating point…), the subtype (after the dot) says what it represents and in which unit. For each group you find the format below, then for each DPT the meaning and, in the table under the description, the parameters: what each one contains and which component Manager creates for it with Create components.
In the KNX Datapoint component, the DPT parameters appear in the Parameters table with the same names (b, c, v, StepCode, FloatValue…).
DPT 1.x · 1 bit (on/off, true/false)
A single bit, field b: it is 0 or 1. The meaning of the two values changes according to the subtype.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
1.001 | Switch | On/off command or status. 0 = Off · 1 = On
| ||||||
1.002 | Bool | Logical value. 0 = False · 1 = True
| ||||||
1.003 | Enable | Enables a function. 0 = Disable · 1 = Enable
| ||||||
1.004 | Ramp | Ramp (gradual change). 0 = No ramp · 1 = Ramp
| ||||||
1.005 | Alarm | Alarm. 0 = No alarm · 1 = Alarm
| ||||||
1.006 | Binary value | Binary value (e.g. digital input). 0 = Low · 1 = High
| ||||||
1.007 | Step | Step. 0 = Decrease · 1 = Increase
| ||||||
1.008 | Up/down | Shutter and blind movement. 0 = Up · 1 = Down
| ||||||
1.009 | Open/close | Opening and closing. 0 = Open · 1 = Close
| ||||||
1.010 | Start | Start and stop. 0 = Stop · 1 = Start
| ||||||
1.011 | State | State of a function. 0 = Inactive · 1 = Active
| ||||||
1.012 | Invert | Inversion. 0 = Not inverted · 1 = Inverted
| ||||||
1.013 | Dim send style | Dimming transmission mode. 0 = Start/stop · 1 = Cyclic
| ||||||
1.014 | Input source | Source of the value. 0 = Fixed · 1 = Calculated
| ||||||
1.015 | Reset | Reset. 0 = No action · 1 = Reset
| ||||||
1.016 | Ack | Acknowledge (e.g. of an alarm). 0 = No action · 1 = Acknowledge
| ||||||
1.017 | Trigger | Trigger: both values start the same action.
| ||||||
1.018 | Occupancy | Presence in a room. 0 = Unoccupied · 1 = Occupied
| ||||||
1.019 | Window Door | Window or door status. 0 = Closed · 1 = Open
| ||||||
1.021 | Logical Function | Logical function. 0 = OR · 1 = AND
| ||||||
1.022 | Scene AB | Scene selection. 0 = Scene A · 1 = Scene B
| ||||||
1.023 | Shutter blinds mode | Shutter control mode. 0 = Up/down only · 1 = Up/down + step/stop
| ||||||
1.024 | Day/night | Day/night. 0 = Day · 1 = Night
| ||||||
1.100 | Heat/cool | Heating or cooling. 0 = Cooling · 1 = Heating
| ||||||
1.1200 | Consumer/producer | Role in the energy system. 0 = Consumer · 1 = Producer
| ||||||
1.1201 | Energy direction | Direction of energy flow. 0 = Positive · 1 = Negative
|
DPT 2.x · 1 bit with priority (control)
Two bits. c (control): 0 = no priority, 1 = the value is forced with priority. v (value): the value, with the same meaning as the corresponding DPT 1.x.
DPT | Name | Meaning, values and parameters | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
2.001 | Switch Control | As 1.001 with priority: v has the same values as 1.001, c = 1 forces the value.
| |||||||||
2.002 | Bool Control | As 1.002 with priority: v has the same values as 1.002, c = 1 forces the value.
| |||||||||
2.003 | Enable Control | As 1.003 with priority: v has the same values as 1.003, c = 1 forces the value.
| |||||||||
2.004 | Ramp Control | As 1.004 with priority: v has the same values as 1.004, c = 1 forces the value.
| |||||||||
2.005 | Alarm Control | As 1.005 with priority: v has the same values as 1.005, c = 1 forces the value.
| |||||||||
2.006 | Binary value Control | As 1.006 with priority: v has the same values as 1.006, c = 1 forces the value.
| |||||||||
2.007 | Step Control | As 1.007 with priority: v has the same values as 1.007, c = 1 forces the value.
| |||||||||
2.008 | Direction1 Control | As 1.008 with priority: v has the same values as 1.008, c = 1 forces the value.
| |||||||||
2.009 | Direction2 Control | As 1.009 with priority: v has the same values as 1.009, c = 1 forces the value.
| |||||||||
2.010 | Start Control | As 1.010 with priority: v has the same values as 1.010, c = 1 forces the value.
| |||||||||
2.011 | State Control | As 1.011 with priority: v has the same values as 1.011, c = 1 forces the value.
| |||||||||
2.012 | Invert Control | As 1.012 with priority: v has the same values as 1.012, c = 1 forces the value.
|
DPT 3.x · 4 bit: relative adjustment (dimming, blinds)
c: direction (3.007: 0 = decrease, 1 = increase · 3.008: 0 = up, 1 = down). StepCode: step size, 0 = stop; from 1 to 7 the step is 100 %, 50 %, 25 %, 12.5 %, 6.25 %, 3.13 %, 1.56 %.
DPT | Name | Meaning, values and parameters | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
3.007 | Control Dimming | Relative dimming: increases or decreases brightness in steps.
| |||||||||
3.008 | Control Blinds | Relative step movement of blinds and curtains.
|
DPT 4.x · Character
One byte, field Character: a single character.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
4.001 | Char ASCII | An ASCII character.
| ||||||
4.002 | Char 8859 1 | An ISO 8859-1 character (with accented letters).
|
DPT 5.x · 8-bit unsigned
One byte, field UnsignedValue (0–255). The Manager converts it to the unit of the subtype (e.g. 0–100 % for 5.001).
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
5.001 | Scaling | Percentage 0–100 % (e.g. brightness, position). The bus value ranges from 0 to 255.
| ||||||
5.003 | Angle | Angle 0–360° (e.g. color hue).
| ||||||
5.004 | Percent U8 | Percentage 0–255 %.
| ||||||
5.005 | Decimalfactor | Ratio or factor 0–255.
| ||||||
5.006 | Tariff | Active tariff (number 0–254).
| ||||||
5.010 | Value 1 Ucount | Pulse counter 0–255.
|
DPT 6.x · 8-bit signed
One byte, field SignedValue (−128…127). DPT 6.020 instead uses fields a–e (status bits) and f (mode).
DPT | Name | Meaning, values and parameters | ||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
6.001 | Percent V8 | Signed percentage −128…127 %: the SignedValue field is used (the a–f fields shown in the list are only for 6.020).
| ||||||||||||||||||||||||
6.010 | Value 1 Count | Signed pulse counter −128…127.
| ||||||||||||||||||||||||
6.020 | Status Mode3 | Status with mode: fields a–e are five status bits, f indicates the active mode (0, 1 or 2).
|
DPT 7.x · 2-byte unsigned
Two bytes, field UnsignedValue (0–65 535), in the unit of the subtype.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
7.001 | Value 2 Ucount | Pulse counter 0–65 535.
| ||||||
7.002 | Timeperiodmsec | Duration in milliseconds (0–65 535 ms).
| ||||||
7.003 | Timeperiod10msec | Duration in tens of milliseconds (0–655.35 s).
| ||||||
7.004 | Timeperiod100msec | Duration in hundreds of milliseconds (0–6 553.5 s).
| ||||||
7.005 | Timeperiodsec | Duration in seconds (0–65 535 s).
| ||||||
7.006 | Timeperiodmin | Duration in minutes (0–65 535 min).
| ||||||
7.007 | Timeperiodhrs | Duration in hours (0–65 535 h).
| ||||||
7.010 | Propdatatype | Identifier of the data type of a KNX property.
| ||||||
7.011 | Length MM | Length in millimeters (0–65 535 mm).
| ||||||
7.012 | Ueicurrentma | Current in milliamperes (0–65 535 mA).
| ||||||
7.013 | Brightness | Brightness in lux (0–65 535 lx).
| ||||||
7.600 | Absolute Colour Temperature | White light color temperature in kelvin (0–65 535 K, e.g. 2 700 K warm light).
|
DPT 8.x · signed 2 byte
Two bytes, SignedValue field (−32 768…32 767), in the unit of the subtype.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
8.001 | Value 2 Count | Signed pulse counter (−32 768…32 767).
| ||||||
8.002 | Deltatimemsec | Time difference in milliseconds (signed).
| ||||||
8.003 | Deltatime10msec | Time difference in tenths of a millisecond (signed).
| ||||||
8.004 | Deltatime100msec | Time difference in hundreds of milliseconds (signed).
| ||||||
8.005 | Deltatimesec | Time difference in seconds (signed).
| ||||||
8.006 | Deltatimemin | Time difference in minutes (signed).
| ||||||
8.007 | Deltatimehrs | Time difference in hours (signed).
| ||||||
8.010 | Percent V16 | Signed percentage (−327.68…327.67 %).
| ||||||
8.011 | Rotation Angle | Rotation angle in degrees (−32 768…32 767°).
| ||||||
8.012 | Length M | Length in meters (signed).
|
DPT 9.x · 2 byte floating point (temperature, lux, speed…)
Two-byte KNX floating point, FloatValue field (from −671 088.64 to 670 760.96 with 0.01 precision). These are the DPTs most commonly used for sensor measurements.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
9.001 | Value Temp | Temperature in °C (e.g. room temperature, setpoint).
| ||||||
9.002 | Value Tempd | Temperature difference in K (e.g. setpoint offset).
| ||||||
9.003 | Value Tempa | Temperature change in K/h.
| ||||||
9.004 | Value Lux | Illuminance in lux.
| ||||||
9.005 | Value Wsp | Wind speed in m/s.
| ||||||
9.006 | Value Pres | Pressure in Pa.
| ||||||
9.007 | Value Humidity | Relative humidity in %.
| ||||||
9.008 | Value Airquality | Air quality in ppm (e.g. CO₂).
| ||||||
9.009 | Value Airflow | Air flow rate in m³/h.
| ||||||
9.010 | Value Time1 | Time in seconds.
| ||||||
9.011 | Value Time2 | Time in milliseconds.
| ||||||
9.020 | Value Volt | Voltage in mV.
| ||||||
9.021 | Value Curr | Current in mA.
| ||||||
9.022 | Powerdensity | Power density in W/m² (e.g. solar irradiance).
| ||||||
9.023 | Kelvinperpercent | Coefficient in K/%.
| ||||||
9.024 | Power | Power in kW.
| ||||||
9.025 | Value Volume Flow | Flow rate in l/h.
| ||||||
9.026 | Rain Amount | Rainfall amount in l/m².
| ||||||
9.027 | Value Temp F | Temperature in °F.
| ||||||
9.028 | Value Wsp Kmh | Wind speed in km/h.
| ||||||
9.029 | Value Absolute Humidity | Absolute humidity in g/m³.
| ||||||
9.030 | Concentration µGM3 | Concentration in µg/m³ (e.g. fine dust).
|
DPT 10.x · Time of day
Fields Day (0 = no day, 1 = Monday … 7 = Sunday), Hour (0–23), Minutes (0–59), Seconds (0–59).
DPT | Name | Meaning, values and parameters | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
10.001 | Timeofday | Time of day with day of week.
|
DPT 11.x · Date
Fields Day (1–31), Month (1–12), Year (0–99: 90–99 = 1990–1999, 0–89 = 2000–2089).
DPT | Name | Meaning, values and parameters | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
11.001 | Date | Date.
|
DPT 12.x · 4-byte unsigned
Four bytes, UnsignedValue field (0–4 294 967 295), in the subtype unit.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
12.001 | Value 4 Ucont | Pulse counter 0–4 294 967 295.
| ||||||
12.100 | Longtimeperiod SEC | Long duration in seconds.
| ||||||
12.101 | Longtimeperiod MIN | Long duration in minutes.
| ||||||
12.102 | Longtimeperiod HRS | Long duration in hours.
| ||||||
12.1200 | Volumeliquid Litre | Liquid volume in liters.
| ||||||
12.1201 | Volume M3 | Volume in m³.
|
DPT 13.x · 4-byte signed (energy, counters)
Four bytes, SignedValue field (−2 147 483 648…2 147 483 647), in the subtype unit. These are the typical DPTs for energy counters.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
13.001 | Value 4 Count | Signed pulse counter (32-bit).
| ||||||
13.002 | Flowrate M3 H | Flow rate in m³/h (resolution 0.0001).
| ||||||
13.010 | Activeenergy | Active energy in Wh.
| ||||||
13.011 | Apparantenergy | Apparent energy in VAh.
| ||||||
13.012 | Reactiveenergy | Reactive energy in VARh.
| ||||||
13.013 | Activeenergy KWH | Active energy in kWh.
| ||||||
13.014 | Apparantenergy KVAH | Apparent energy in kVAh.
| ||||||
13.015 | Reactiveenergy KVARH | Reactive energy in kVARh.
| ||||||
13.016 | Activeenergy MWH | Active energy in MWh.
| ||||||
13.017 | Longdeltatimesec | Long time difference in seconds.
| ||||||
13.1200 | Deltavolumeliquid Litre | Change in liquid volume in liters.
| ||||||
13.1201 | Deltavolume M3 | Change in volume in m³.
|
DPT 14.x · 4-byte floating point (physical quantities)
Four-byte IEEE 754 floating point, FloatValue field, in the indicated International System unit.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
14.000 | Value Acceleration | Acceleration (m/s²).
| ||||||
14.001 | Value Acceleration Angular | Angular acceleration (rad/s²).
| ||||||
14.002 | Value Activation Energy | Activation energy (J/mol).
| ||||||
14.003 | Value Activity | Radioactive activity (1/s).
| ||||||
14.004 | Value Mol | Amount of substance (mol).
| ||||||
14.005 | Value Amplitude | Amplitude.
| ||||||
14.006 | Value Anglerad | Angle (rad).
| ||||||
14.007 | Value Angledeg | Angle (°).
| ||||||
14.008 | Value Angular Momentum | Angular momentum (J·s).
| ||||||
14.009 | Value Angular Velocity | Angular velocity (rad/s).
| ||||||
14.010 | Value Area | Area (m²).
| ||||||
14.011 | Value Capacitance | Capacitance (F).
| ||||||
14.012 | Value Charge Densitysurface | Surface charge density (C/m²).
| ||||||
14.013 | Value Charge Densityvolume | Volume charge density (C/m³).
| ||||||
14.014 | Value Compressibility | Compressibility (m²/N).
| ||||||
14.015 | Value Conductance | Conductance (S).
| ||||||
14.016 | Value Electrical Conductivity | Electrical conductivity (S/m).
| ||||||
14.017 | Value Density | Density (kg/m³).
| ||||||
14.018 | Value Electric Charge | Electric charge (C).
| ||||||
14.019 | Value Electric Current | Electric current (A).
| ||||||
14.020 | Value Electric Currentdensity | Current density (A/m²).
| ||||||
14.021 | Value Electric Dipolemoment | Electric dipole moment (C·m).
| ||||||
14.022 | Value Electric Displacement | Electric displacement (C/m²).
| ||||||
14.023 | Value Electric Fieldstrenght | Electric field strength (V/m).
| ||||||
14.024 | Value Electric Flux | Electric flux (V·m).
| ||||||
14.025 | Value Electric Fluxdensity | Electric flux density (C/m²).
| ||||||
14.026 | Value Electric Polarization | Electric polarization (C/m²).
| ||||||
14.027 | Value Electric Potential | Electric potential (V).
| ||||||
14.028 | Value Electric Potentialdifference | Potential difference (V).
| ||||||
14.029 | Value Electromagneticmoment | Electromagnetic moment (A·m²).
| ||||||
14.030 | Value Electromotive Force | Electromotive force (V).
| ||||||
14.031 | Value Energy | Energy (J).
| ||||||
14.032 | Value Force | Force (N).
| ||||||
14.033 | Value Frequency | Frequency (Hz).
| ||||||
14.034 | Value Angular Frequency | Angular frequency (rad/s).
| ||||||
14.035 | Value Heat Capacity | Heat capacity (J/K).
| ||||||
14.036 | Value Heat Flowrate | Heat flow (W).
| ||||||
14.037 | Value Heat Quantity | Heat quantity (J).
| ||||||
14.038 | Value Impedance | Impedance (Ω).
| ||||||
14.039 | Value Length | Length (m).
| ||||||
14.040 | Value Light Quantity | Light quantity (lm·s).
| ||||||
14.041 | Value Luminance | Luminance (cd/m²).
| ||||||
14.042 | Value Luminous Flux | Luminous flux (lm).
| ||||||
14.043 | Value Luminous Intensity | Luminous intensity (cd).
| ||||||
14.044 | Value Magnetic Fieldstrength | Magnetic field strength (A/m).
| ||||||
14.045 | Value Magnetic Flux | Magnetic flux (Wb).
| ||||||
14.046 | Value Magnetic Fluxdensity | Magnetic flux density (T).
| ||||||
14.047 | Value Magnetic Moment | Magnetic moment (A·m²).
| ||||||
14.048 | Value Magnetic Polarization | Magnetic polarization (T).
| ||||||
14.049 | Value Magnetization | Magnetization (A/m).
| ||||||
14.050 | Value Magnetomotiveforce | Magnetomotive force (A).
| ||||||
14.051 | Value Mass | Mass (kg).
| ||||||
14.052 | Value Massflux | Mass flow rate (kg/s).
| ||||||
14.053 | Value Momentum | Momentum (kg·m/s).
| ||||||
14.054 | Value Phase Anglerad | Phase angle (rad).
| ||||||
14.055 | Value Phase Angledeg | Phase angle (°).
| ||||||
14.056 | Value Power | Power (W).
| ||||||
14.057 | Value Power Factor | Power factor (cos φ).
| ||||||
14.058 | Value Pressure | Pressure (Pa).
| ||||||
14.059 | Value Reactance | Reactance (Ω).
| ||||||
14.060 | Value Resistance | Resistance (Ω).
| ||||||
14.061 | Value Resistivity | Resistivity (Ω·m).
| ||||||
14.062 | Value Selfinductance | Inductance (H).
| ||||||
14.063 | Value Solidangle | Solid angle (sr).
| ||||||
14.064 | Value Sound Intensity | Sound intensity (W/m²).
| ||||||
14.065 | Value Speed | Speed (m/s).
| ||||||
14.066 | Value Stress | Mechanical stress (Pa).
| ||||||
14.067 | Value Surface Tension | Surface tension (N/m).
| ||||||
14.068 | Value Common Temperature | Temperature (°C).
| ||||||
14.069 | Value Absolute Temperature | Absolute temperature (K).
| ||||||
14.070 | Value Temperaturedifference | Temperature difference (K).
| ||||||
14.071 | Value Thermal Capacity | Thermal capacity (J/K).
| ||||||
14.072 | Value Thermal Conductivity | Thermal conductivity (W/(m·K)).
| ||||||
14.073 | Value Thermoelectricpower | Thermoelectric coefficient (V/K).
| ||||||
14.074 | Value Time | Time (s).
| ||||||
14.075 | Value Torque | Torque (N·m).
| ||||||
14.076 | Value Volume | Volume (m³).
| ||||||
14.077 | Value Volume Flux | Volume flow rate (m³/s).
| ||||||
14.078 | Value Weight | Weight (N).
| ||||||
14.079 | Value Work | Work (J).
| ||||||
14.080 | Value Apparentpower | Apparent power (VA).
| ||||||
14.1200 | Volume Flux Meter | Volume flow rate (m³/h).
| ||||||
14.1201 | Volume Flux LS | Volume flow rate (l/s).
|
DPT 15.x · Access data
Fields D6–D1: the six digits of the code (0–9). E: read error (1 = error). P: permission (1 = access granted). D: read direction. C: encrypted code (1 = yes). Index: reader index (0–15).
DPT | Name | Meaning, values and parameters | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
15.000 | Access Data | Access reader data (badge, code).
|
DPT 16.x · 14-character string
Field String: text up to 14 characters; unused characters are filled with zeros.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
16.000 | String ASCII | Text up to 14 ASCII characters.
| ||||||
16.001 | String 8859 1 | Text up to 14 ISO 8859-1 characters.
|
DPT 17.x · Scene number
Field SceneNumber: 0–63 (corresponds to scenes 1–64 usually indicated in ETS and on push buttons).
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
17.001 | Scenenumber | Scene number to recall (0–63, on the display 1–64).
|
DPT 18.x · Scene control
SceneNumber: 0–63. C: 0 = recall the scene, 1 = store the current state in the scene (learn).
DPT | Name | Meaning, values and parameters | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
18.001 | Scenecontrol | Recall or store a scene.
|
DPT 19.x · Date and time
Fields Year (1900–2155), Month, DayOfMonth, DayOfWeek (0 = none, 1 = Monday … 7 = Sunday), HourOfDay (0–24), Minutes, Seconds, plus flags (1 = true): F fault · WD workday · NWD invalid workday · NY invalid year · ND invalid date · NDoW invalid day of week · NT invalid time · SUTI daylight saving time · CLQ clock synchronized with an external source · SRC synchronization reliability.
DPT | Name | Meaning, values and parameters | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
19.001 | Datetime | Full date and time.
|
DPT 20.x · 8-bit enumeration (HVAC modes, states…)
One byte, field field1: a number corresponding to an entry in a list. The Combo component shows the entries with their name.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
20.001 | Sclomode | System mode (SCLO): 0 = autonomous · 1 = slave · 2 = master.
| ||||||
20.002 | Buildingmode | Building mode: 0 = in use · 1 = not in use · 2 = protection.
| ||||||
20.003 | Occmode | Occupancy: 0 = occupied · 1 = standby · 2 = unoccupied.
| ||||||
20.004 | Priority | Priority: 0 = high · 1 = medium · 2 = low · 3 = none.
| ||||||
20.005 | Lightapplicationmode | Lighting mode: 0 = normal · 1 = presence simulation · 2 = night round.
| ||||||
20.006 | Applicationarea | Application area (HVAC, lighting, security, blinds…) of a message or alarm.
| ||||||
20.007 | Alarmclasstype | Alarm class: 1 = simple · 2 = basic · 3 = extended.
| ||||||
20.008 | Psumode | Power supply mode: 0 = off · 1 = on · 2 = automatic.
| ||||||
20.011 | Errorclass System | System error class (0 = no fault, then error type).
| ||||||
20.012 | Errorclass HVAC | HVAC error class: 0 = no fault · 1 = sensor · 2 = control · 3 = actuator · 4 = other.
| ||||||
20.013 | Time Delay | Encoded delay: 0 = inactive, then from 1 s up to 24 h.
| ||||||
20.014 | Beaufort Wind Force Scale | Wind force on the Beaufort scale (0–12).
| ||||||
20.017 | Sensorselect | Type of sensor connected to an input.
| ||||||
20.020 | Actuatorconnecttype | Actuator connection type: 1 = sensor · 2 = controller.
| ||||||
20.021 | Cloud Cover | Cloud cover in okta: 0 = clear … 8 = overcast · 9 = sky not visible.
| ||||||
20.022 | Powerreturnmode | Transmission after voltage return: 0 = do not send · 1 = always send · 2 = send if changed.
| ||||||
20.100 | Fueltype | Fuel: 0 = automatic · 1 = diesel · 2 = gas · 3 = solid.
| ||||||
20.101 | Burnertype | Burner: 1 = single-stage · 2 = two-stage · 3 = modulating.
| ||||||
20.102 | Hvacmode | HVAC mode: 0 = Auto · 1 = Comfort · 2 = Standby · 3 = Economy · 4 = Building protection.
| ||||||
20.103 | Dhwmode | Domestic hot water mode: 0 = Auto · 1 = anti-legionella · 2 = normal · 3 = reduced · 4 = off/anti-freeze.
| ||||||
20.104 | Loadpriority | Load priority: 0 = none · 1 = shift · 2 = absolute.
| ||||||
20.105 | Hvaccontrmode | HVAC control mode: 0 = Auto · 1 = heating · 2 = morning preheating · 3 = cooling · 4 = night purge · 5 = pre-cooling · 6 = off · 7 = test · 8 = emergency heating · 9 = ventilation only · 10 = free cooling · 11 = ice · 12 = maximum heating · 13 = economy · 14 = dehumidification · 15 = calibration · 16 = emergency cooling · 17 = emergency steam · 20 = no request.
| ||||||
20.106 | Hvacemergmode | Emergency mode: 0 = normal · 1 = pressurization · 2 = depressurization · 3 = purge · 4 = stop · 5 = fire.
| ||||||
20.107 | Changeovermode | Seasonal changeover: 0 = Auto · 1 = cooling only · 2 = heating only.
| ||||||
20.108 | Valvemode | Valve mode (heating/cooling stages on/off or modulating).
| ||||||
20.109 | Dampermode | Damper mode (outside air, supply air, return air…).
| ||||||
20.110 | Heatermode | Heater mode (on/off or proportional stages).
| ||||||
20.111 | Fanmode | Fan: 0 = stopped · 1 = always on · 2 = intermittently.
| ||||||
20.112 | Masterslavemode | Role: 0 = standalone · 1 = master · 2 = slave.
| ||||||
20.113 | Statusroomsetp | Setpoint in use: 0 = normal · 1 = alternative · 2 = building protection.
| ||||||
20.114 | Metering Devicetype | Meter type (electricity, gas, water, heat…).
| ||||||
20.115 | Humdehummode | Humidification/dehumidification: 0 = inactive · 1 = humidify · 2 = dehumidify.
| ||||||
20.120 | Adatype | Air actuator type: 1 = damper · 2 = VAV.
| ||||||
20.121 | Backupmode | Backup behavior: 0 = fallback value · 1 = keeps last state.
| ||||||
20.122 | Startsynchronization | Start-up synchronization: 0 = position unchanged · 1 = close · 2 = open.
| ||||||
20.600 | Behaviour Lock Unlock | Lock/unlock behavior (off, on, unchanged, stored value…).
| ||||||
20.601 | Behaviour Bus Power Up Down | Behavior on bus voltage loss and restoration.
| ||||||
20.602 | DALI Fade Time | DALI fade time (code 0–15).
| ||||||
20.603 | Blinkingmode | Blinking: 0 = disabled · 1 = without confirmation · 2 = with confirmation.
| ||||||
20.604 | Lightcontrolmode | Light control: 0 = automatic · 1 = manual.
| ||||||
20.605 | Switchpbmodel | Pushbutton model: 1 = single button · 2 = two buttons.
| ||||||
20.606 | Pbaction | Pushbutton action: 0 = none · 1 = turn off · 2 = turn on · 3 = toggle on each press.
| ||||||
20.607 | Dimmpbmodel | Dimming pushbutton model (one or two buttons).
| ||||||
20.608 | Switchonmode | Switch-on: 0 = last value · 1 = parameter value · 2 = last absolute value received.
| ||||||
20.609 | Loadtypeset | Configured load type: 0 = automatic · 1 = leading-edge phase cut · 2 = trailing-edge phase cut.
| ||||||
20.610 | Loadtypedetected | Detected load type: 0 = undefined · 1 = leading-edge · 2 = trailing-edge · 3 = detection not possible.
| ||||||
20.611 | Converter Test Control | DALI emergency converter test command (functional test, endurance test, stop…).
| ||||||
20.612 | Converter Control | DALI emergency converter command.
| ||||||
20.613 | Converter Data Request | Data request to the DALI emergency converter.
| ||||||
20.801 | Sabexceptbehaviour | Shutter behavior in case of exception (up, down, unchanged, stop…).
| ||||||
20.802 | Sabbehaviour Lock Unlock | Shutter behavior when locking/unlocking.
| ||||||
20.803 | Sssbmode | Shutter control mode with push-buttons.
| ||||||
20.804 | Blindscontrolmode | Shutter control: 0 = automatic · 1 = manual.
| ||||||
20.1000 | Commmode | Interface communication mode (data layer, bus monitor…).
| ||||||
20.1001 | Addinfotypes | Type of additional information in telegrams.
| ||||||
20.1002 | RF Modeselect | KNX RF radio mode: 0 = asynchronous · 1 = BiBat master · 2 = BiBat slave.
| ||||||
20.1003 | RF Filterselect | KNX RF radio filter (by domain address and/or serial number).
| ||||||
20.1004 | Medium | KNX medium: 0 = TP1 · 1 = PL110 · 2 = RF · 5 = KNX IP.
| ||||||
20.1005 | PB Function | Push-button function.
| ||||||
20.1200 | MBUS Breaker Valve State | M-Bus breaker/valve state: 0 = closed · 1 = open · 2 = unlocked.
| ||||||
20.1202 | Gas Measurement Condition | Gas measurement conditions: 0 = unknown · 1 = converted to temperature · 2 = base conditions · 3 = measurement conditions.
| ||||||
20.1203 | Breaker Status | Meter breaker status: 0 = closed · then opened due to overload, overvoltage, load disconnection, command, overheating.
| ||||||
20.1204 | Euridis Communication Interface Status | Euridis interface status: 0 = disabled · 1 = enabled.
| ||||||
20.1205 | PLC Status | Meter PLC communication status.
| ||||||
20.1206 | Peak Event Notice | Peak event notice (tariffs with peak days).
| ||||||
20.1207 | Peak Event | Peak event in progress.
| ||||||
20.1208 | TIC Type | Meter TIC output type (historical or standard).
| ||||||
20.1209 | Type TIC Channel | TIC channel type.
|
DPT 21.x · 8 bit bit set (statuses)
Fields b0–b7: eight independent bits, each one a status flag (1 = active).
DPT | Name | Meaning, values and parameters | |||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21.001 | Statusgen | General status: b0 out of service · b1 fault · b2 forced · b3 in alarm · b4 alarm not acknowledged.
| |||||||||||||||||||||||||||
21.002 | Device Control | Device control: b0 application stopped · b1 own address · b2 verify mode.
| |||||||||||||||||||||||||||
21.100 | Forcesign | Heating override signal (request, protection, excess supply, domestic hot water, comfort…).
| |||||||||||||||||||||||||||
21.101 | Forcesigncool | Cooling override signal: b0 forced request.
| |||||||||||||||||||||||||||
21.102 | Statusrhc | Heating controller status: b0 fault · b1 eco · b2 supply limit · b3 return limit · b4 morning boost · b5/b6 start/stop optimization · b7 summer mode.
| |||||||||||||||||||||||||||
21.103 | Statussdhwc | Solar domestic hot water status: b0 fault · b1 solar charging active · b2 sufficient solar energy.
| |||||||||||||||||||||||||||
21.104 | Fueltypeset | Available fuels: b0 diesel · b1 gas · b2 solid.
| |||||||||||||||||||||||||||
21.105 | Statusrcc | Cooling controller status: b0 fault.
| |||||||||||||||||||||||||||
21.106 | Statusahu | Air handling unit status: b0 fault · b1 fan active · b2 heating · b3 cooling.
| |||||||||||||||||||||||||||
21.601 | Lightactuatorerrorinfo | Light actuator errors: load not detected, undervoltage, overcurrent, underload, faulty load, lamp failure, overheating.
| |||||||||||||||||||||||||||
21.1000 | RF Modeinfo | Information on KNX RF radio mode.
| |||||||||||||||||||||||||||
21.1001 | RF Filterinfo | Information on the KNX RF radio filter.
| |||||||||||||||||||||||||||
21.1002 | Security Report | Security report: b0 attack attempt detected.
| |||||||||||||||||||||||||||
21.1010 | Channel Activation 8 | Activation of 8 channels: b0–b7 = channels 1–8.
| |||||||||||||||||||||||||||
21.1200 | Virtualdrycontact | Virtual dry contacts: b0–b7 = contact status 1–8.
| |||||||||||||||||||||||||||
21.1201 | Phases Status | Phase presence: b0 L1 · b1 L2 · b2 L3.
|
DPT 22.x · 16-bit bit set
16-bit UnsignedValue field: each bit is a status flag.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
22.100 | Statusdhwc | Domestic hot water generator status (16 bits: fault, active charging, anti-legionella, solar energy…).
| ||||||
22.101 | Statusrhcc | Heating/cooling controller status (16 bits).
| ||||||
22.1000 | Media | Supported communication media (TP1, PL110, RF, IP).
| ||||||
22.1010 | Channel Activation 16 | Activation of 16 channels (one bit per channel).
|
DPT 23.x · 2-bit enumeration
Field s: a value from 0 to 3 with the specified meaning.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
23.001 | Onoffaction | On/off action: 0 = Off · 1 = On · 2 = Off/On · 3 = On/Off.
| ||||||
23.002 | Alarm Reaction | Shutter alarm reaction: 0 = none · 1 = alarm position up · 2 = alarm position down.
| ||||||
23.003 | Updown Action | Up/down action: 0 = Up · 1 = Down · 2 = Up/Down · 3 = Down/Up.
| ||||||
23.102 | HVAC PB Action | HVAC pushbutton action: 0 = Comfort/Economy · 1 = Comfort/none · 2 = Economy/none · 3 = Building protection/Auto.
|
DPT 24.x · Variable-length string
Field String: variable-length text.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
24.001 | Varstring 8859 1 | Variable-length ISO 8859-1 text.
|
DPT 25.x · Double nibble
Fields Busy and Nak: two counters from 0 to 15.
DPT | Name | Meaning, values and parameters | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
25.1000 | Doublenibble | Double repetition counter (Busy and Nak, 0–15 each).
|
DPT 26.x · Scene information
SceneNumber: 0–63. B: 0 = active scene, 1 = inactive scene.
DPT | Name | Meaning, values and parameters | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
26.001 | Sceneinfo | Scene information: number and active/inactive status.
|
DPT 27.x · Combined on/off states
Fields s0–s15: on/off status of outputs 1–16. m0–m15: mask, 1 = the status of the corresponding output is valid.
DPT | Name | Meaning, values and parameters | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
27.001 | Combinedinfoonoff | On/off status of 16 outputs in a single telegram, with validity mask.
|
DPT 28.x · Unicode string (UTF-8)
Field String: variable-length UTF-8 text (accepts any language).
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
28.001 | Uft 8 | Variable-length UTF-8 text.
|
DPT 29.x · 8-byte signed value (V64 energy)
Eight bytes, field SignedValue: energy counters of large plants.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
29.010 | Activeenergy V64 | Active energy in Wh (64-bit, for large-plant meters).
| ||||||
29.011 | Apparantenergy V64 | Apparent energy in VAh (64-bit).
| ||||||
29.012 | Reactiveenergy V64 | Reactive energy in VARh (64-bit).
|
DPT 30.x · 24-channel activation
Fields b0–b23: one bit for each of the 24 channels.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
30.1010 | Channel Activation 24 | Activation of 24 channels (one bit per channel).
|
DPT 31.x · Extended HVAC push-button actions
Field s: the push-button action on HVAC modes.
DPT | Name | Meaning, values and parameters | ||||||
|---|---|---|---|---|---|---|---|---|
31.101 | PB Action HVAC Extended | Extended HVAC push-button action (Comfort, Standby, Economy, Building protection modes).
|
DPT 200–284 · Composite types (HVAC, meters, DALI, colors, energy…)
147 DPT. These DPTs carry multiple values in the same telegram: the Manager creates one component for each field. Field names often repeat:
Field | Meaning |
|---|---|
Value / UnsignedValue / SignedValue | The main value, in the DPT unit. |
StatusCommand | Status byte accompanying the value (fault, out of service, forced, alarm…). DPTs with «Z» in the name have this field. |
Attributes | Flags describing the value (validity, source, limits). |
Mode / DelayTime | The next mode and how many minutes until it becomes active. |
TempSetp… | Setpoint (or setpoint shift) for Comfort, Standby, Economy, Building protection. |
R, G, B, W · MR, MG, MB, MW | Color components 0–255 and related validity masks. |
C… / StepCode… | Direction and size of the step in relative adjustments (as in DPT 3.x). |
Year … Seconds, F | Date and time with quality flag (as in DPT 19.001). |
Phase1, Phase2, Phase3 | Value on each of the three phases. |
Mask, Probability | In forecasts: which fields are valid and the probability (%). |
DPT | Name | Meaning, values and parameters | ||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
200.100 | Heatcool Z | Heating/cooling with status byte.
| ||||||||||||||||||||||||||||||
200.101 | Binaryvalue Z | Binary value with status byte.
| ||||||||||||||||||||||||||||||
201.100 | Hvacmode Z | HVAC mode (as 20.102) with status byte.
| ||||||||||||||||||||||||||||||
201.102 | Dhwmode Z | Domestic hot water mode (as 20.103) with status byte.
| ||||||||||||||||||||||||||||||
201.104 | Hvaccontrmode Z | HVAC control mode (as 20.105) with status byte.
| ||||||||||||||||||||||||||||||
201.105 | Enablehc Stage Z | Enabling of heating/cooling stages with status byte.
| ||||||||||||||||||||||||||||||
201.107 | Buildingmode Z | Building mode (as 20.002) with status byte.
| ||||||||||||||||||||||||||||||
201.108 | Occmode Z | Occupancy (as 20.003) with status byte.
| ||||||||||||||||||||||||||||||
201.109 | Hvacemergmode Z | HVAC emergency mode (as 20.106) with status byte.
| ||||||||||||||||||||||||||||||
202.001 | Relvalue Z | Relative value 0–255 with status byte.
| ||||||||||||||||||||||||||||||
202.002 | Ucountvalue8 Z | Counter 0–255 with status byte.
| ||||||||||||||||||||||||||||||
203.002 | Timeperiodmsec Z | Duration in ms with status byte.
| ||||||||||||||||||||||||||||||
203.003 | Timeperiod10msec Z | Duration in tenths of ms with status byte.
| ||||||||||||||||||||||||||||||
203.004 | Timeperiod100msec Z | Duration in hundreds of ms with status byte.
| ||||||||||||||||||||||||||||||
203.005 | Timeperiodsec Z | Duration in seconds with status byte.
| ||||||||||||||||||||||||||||||
203.006 | Timeperiodmin Z | Duration in minutes with status byte.
| ||||||||||||||||||||||||||||||
203.007 | Timeperiodhrs Z | Duration in hours with status byte.
| ||||||||||||||||||||||||||||||
203.011 | Uflowrateliter H Z | Flow rate in l/h with status byte.
| ||||||||||||||||||||||||||||||
203.012 | Ucountvalue16 Z | Counter 0–65 535 with status byte.
| ||||||||||||||||||||||||||||||
203.013 | Ueicurrentµa Z | Current in µA with status byte.
| ||||||||||||||||||||||||||||||
203.014 | Powerkw Z | Power in kW with status byte.
| ||||||||||||||||||||||||||||||
203.015 | Atmpressureabs Z | Absolute atmospheric pressure with status byte.
| ||||||||||||||||||||||||||||||
203.017 | Percentu16 Z | Percentage with status byte.
| ||||||||||||||||||||||||||||||
203.100 | Hvacairqual Z | Air quality in ppm with status byte.
| ||||||||||||||||||||||||||||||
203.101 | Windspeed Z | Wind speed with status byte.
| ||||||||||||||||||||||||||||||
203.102 | Sunintensity Z | Solar irradiance with status byte.
| ||||||||||||||||||||||||||||||
203.104 | Hvacairflowabs Z | Absolute air flow with status byte.
| ||||||||||||||||||||||||||||||
204.001 | Relsignedvalue Z | Relative signed value with status byte.
| ||||||||||||||||||||||||||||||
205.002 | Deltatimemsec Z | Time difference in ms with status byte.
| ||||||||||||||||||||||||||||||
205.003 | Deltatime10msec Z | Time difference in tenths of ms with status byte.
| ||||||||||||||||||||||||||||||
205.004 | Deltatime100msec Z | Time difference in hundreds of ms with status byte.
| ||||||||||||||||||||||||||||||
205.005 | Deltatimesec Z | Time difference in seconds with status byte.
| ||||||||||||||||||||||||||||||
205.006 | Deltatimemin Z | Time difference in minutes with status byte.
| ||||||||||||||||||||||||||||||
205.007 | Deltatimehrs Z | Time difference in hours with status byte.
| ||||||||||||||||||||||||||||||
205.017 | Percent V16 Z | Signed percentage with status byte.
| ||||||||||||||||||||||||||||||
205.100 | Temphvacabs Z | Absolute HVAC temperature (°C) with status byte.
| ||||||||||||||||||||||||||||||
205.101 | Temphvacrel Z | Relative HVAC temperature (K) with status byte.
| ||||||||||||||||||||||||||||||
205.102 | Hvacairflowrel Z | Relative air flow rate with status byte.
| ||||||||||||||||||||||||||||||
205.103 | Hvacairqualrel Z | Relative air quality with status byte.
| ||||||||||||||||||||||||||||||
206.100 | Hvacmodenext | Next HVAC mode and in how many minutes it will activate.
| ||||||||||||||||||||||||||||||
206.102 | Dwhmodenext | Next domestic hot water mode and in how many minutes.
| ||||||||||||||||||||||||||||||
206.104 | Occmodenext | Next occupancy and in how many minutes.
| ||||||||||||||||||||||||||||||
206.105 | Buildingmodenext | Next building mode and in how many minutes.
| ||||||||||||||||||||||||||||||
207.100 | Statusbuc | Burner/boiler status.
| ||||||||||||||||||||||||||||||
207.101 | Locksign | Lock signal (lock request).
| ||||||||||||||||||||||||||||||
207.102 | Valuedemboc | Boiler power request (%).
| ||||||||||||||||||||||||||||||
207.104 | Actposdemabs | Requested actuator position (%).
| ||||||||||||||||||||||||||||||
207.105 | Statusact | Actuator status.
| ||||||||||||||||||||||||||||||
207.600 | Statuslightingactuator | Lighting actuator status (level and flag).
| ||||||||||||||||||||||||||||||
209.100 | Statushpm | Heat producer status: temperature and attributes.
| ||||||||||||||||||||||||||||||
209.101 | Temproomdemabs | Requested room temperature and attributes.
| ||||||||||||||||||||||||||||||
209.102 | Statuscpm | Cold producer status: temperature and attributes.
| ||||||||||||||||||||||||||||||
209.103 | Statuswtc | Water temperature controller status.
| ||||||||||||||||||||||||||||||
210.100 | Tempflowwaterdemabs | Requested supply water temperature, with attributes.
| ||||||||||||||||||||||||||||||
211.100 | Energydemwater | Energy request for water and active control mode.
| ||||||||||||||||||||||||||||||
212.100 | Temproomsetpsetshift 3 | Room setpoint offsets for Comfort, Standby and Economy.
| ||||||||||||||||||||||||||||||
212.101 | Temproomsetpset 3 | Room setpoints Comfort, Standby and Economy.
| ||||||||||||||||||||||||||||||
213.100 | Temproomsetpset 4 | Four room setpoints: Comfort, Standby, Economy, Building protection.
| ||||||||||||||||||||||||||||||
213.101 | Tempdhwsetpset 4 | Four domestic hot water setpoints.
| ||||||||||||||||||||||||||||||
213.102 | Temproomsetpsetshift 4 | Four room setpoint shifts.
| ||||||||||||||||||||||||||||||
214.100 | Powerflowwaterdemhpc | Request to the heat generator: supply temperature, relative power limit and attributes.
| ||||||||||||||||||||||||||||||
214.101 | Powerflowwaterdemcpm | Request to the cooling generator: supply temperature, relative power limit and attributes.
| ||||||||||||||||||||||||||||||
215.100 | Statusboc | Boiler status: temperature, attributes and relative power.
| ||||||||||||||||||||||||||||||
215.101 | Statuscc | Chiller status: temperature, attributes and relative power.
| ||||||||||||||||||||||||||||||
216.100 | Specheatprod | Heat generator characteristics: rated power, stages, burner type and fuel type.
| ||||||||||||||||||||||||||||||
217.001 | Version | Version: magic number, version and revision.
| ||||||||||||||||||||||||||||||
218.001 | Volumeliter Z | Volume in liters with status byte.
| ||||||||||||||||||||||||||||||
218.002 | Flowrate M3 H Z | Flow rate in m³/h with status byte.
| ||||||||||||||||||||||||||||||
219.001 | Alarminfo | Alarm information: record number, priority, application area, error class and alarm states.
| ||||||||||||||||||||||||||||||
220.100 | Temphvacabsnext | Next HVAC temperature and when it will be activated.
| ||||||||||||||||||||||||||||||
221.001 | Sernum | KNX serial number: manufacturer code and sequential number.
| ||||||||||||||||||||||||||||||
222.100 | Temproomsetpsetf16 3 | Floating-point Comfort, Standby and Economy setpoints.
| ||||||||||||||||||||||||||||||
222.101 | Temproomsetpsetshiftf16 3 | Floating-point Comfort, Standby and Economy setpoint shifts.
| ||||||||||||||||||||||||||||||
223.100 | Energydemair | Energy demand for air, emergency mode and control mode.
| ||||||||||||||||||||||||||||||
224.100 | Tempsupplyairsetpset | Supply air setpoint in cooling and heating, with modes.
| ||||||||||||||||||||||||||||||
225.001 | Scalingspeed | Rate of change: time and percentage.
| ||||||||||||||||||||||||||||||
225.002 | Scaling Stept Time | Step time of the change and percentage.
| ||||||||||||||||||||||||||||||
225.003 | Tariffnext | Next tariff and when it will be activated.
| ||||||||||||||||||||||||||||||
229.001 | Meteringvalue | Value of a counter with status and quantity type (unit).
| ||||||||||||||||||||||||||||||
230.1000 | MBUS Address | M-Bus address: manufacturer, identification number, version and medium.
| ||||||||||||||||||||||||||||||
231.001 | ASCII Locale | Language and region (two letters each).
| ||||||||||||||||||||||||||||||
232.600 | Colour RGB | RGB color: red, green, blue 0–255.
| ||||||||||||||||||||||||||||||
234.001 | Languagecodealpha2 ASCII | Two-letter language code (ISO 639-1, e.g. it).
| ||||||||||||||||||||||||||||||
234.002 | Regioncodealpha2 ASCII | Two-letter region code (ISO 3166-1, e.g. IT).
| ||||||||||||||||||||||||||||||
235.001 | Tariff Activeenergy | Active energy by tariff: value, tariff number and validity.
| ||||||||||||||||||||||||||||||
236.001 | Prioritised Mode Control | Priority mode control: disable, priority and mode.
| ||||||||||||||||||||||||||||||
237.600 | DALI Control Gear Diagnostic | DALI control gear diagnostics: errors of the converter, ballast and lamp, with address.
| ||||||||||||||||||||||||||||||
238.001 | Sceneconfig | Scene configuration: number and storage and activation options.
| ||||||||||||||||||||||||||||||
238.600 | DALI Diagnostic | DALI diagnostics (status and address).
| ||||||||||||||||||||||||||||||
239.001 | Flaggedscaling | Percentage with validity flag.
| ||||||||||||||||||||||||||||||
240.800 | Combinedposition | Combined position of blinds with slats: height %, slat tilt % and validity.
| ||||||||||||||||||||||||||||||
241.800 | Statussab | Complete status of blinds/sunshades: height, slats and flags (limit switches, obstacle, override, wind/rain alarms…).
| ||||||||||||||||||||||||||||||
242.600 | Colour XYY | Color in the xyY space: x and y coordinates, brightness and validity flag.
| ||||||||||||||||||||||||||||||
243.600 | Colour Transition XYY | xyY color transition with time.
| ||||||||||||||||||||||||||||||
244.600 | Converter Status | Status of the DALI emergency converter (mode, pending test, faults).
| ||||||||||||||||||||||||||||||
245.600 | Converter Test Result | Emergency DALI converter test result.
| ||||||||||||||||||||||||||||||
246.600 | Battery Info | Battery status and charge level.
| ||||||||||||||||||||||||||||||
247.600 | Converter Test Info | Information on the emergency converter test (date and durations).
| ||||||||||||||||||||||||||||||
248.600 | Converter Info Fix | Fixed emergency converter characteristics (levels, rated duration).
| ||||||||||||||||||||||||||||||
249.600 | Brightness Colour Temperature Transition | Brightness and color temperature transition.
| ||||||||||||||||||||||||||||||
251.600 | Colour RGBW | RGBW color: red, green, blue, white 0–255 and validity masks.
| ||||||||||||||||||||||||||||||
252.600 | Relative Control RGBW | Relative RGBW control: direction and step for each color.
| ||||||||||||||||||||||||||||||
253.600 | Relative Control XYY | Relative xyY control: saturation, color, and brightness.
| ||||||||||||||||||||||||||||||
254.600 | Relative Control RGB | Relative RGB control: direction and step for each color.
| ||||||||||||||||||||||||||||||
255.001 | Geographicallocation | Geographic location: longitude and latitude.
| ||||||||||||||||||||||||||||||
256.001 | Datetime Period | Period with start and end date and time.
| ||||||||||||||||||||||||||||||
257.1200 | Value Electric Current 3 | Current on the three phases.
| ||||||||||||||||||||||||||||||
257.1201 | Value Electric Potential 3 | Voltage on the three phases.
| ||||||||||||||||||||||||||||||
257.1202 | Value Apparentpower 3 | Apparent power on the three phases.
| ||||||||||||||||||||||||||||||
265.001 | Datetime Switch | Date and time with on/off value.
| ||||||||||||||||||||||||||||||
265.005 | Datetime Alarm | Date and time with alarm.
| ||||||||||||||||||||||||||||||
265.009 | Datetime Openclose | Date and time with open/close.
| ||||||||||||||||||||||||||||||
265.011 | Datetime State | Date and time with active/inactive state.
| ||||||||||||||||||||||||||||||
265.012 | Datetime Invert | Date and time with inversion.
| ||||||||||||||||||||||||||||||
265.1200 | Datetime Consumerproducer | Date and time with consumer/producer.
| ||||||||||||||||||||||||||||||
265.1201 | Datetime Energydirection | Date and time with energy direction.
| ||||||||||||||||||||||||||||||
266.027 | Datetime Value Electric Potential | Date and time with voltage.
| ||||||||||||||||||||||||||||||
266.056 | Datetime Value Power | Date and time with power.
| ||||||||||||||||||||||||||||||
266.080 | Datetime Value Apparentpower | Date and time with apparent power.
| ||||||||||||||||||||||||||||||
267.001 | Datetime UTF 8 | Date and time with UTF-8 text.
| ||||||||||||||||||||||||||||||
268.1203 | Datetime Breaker Status | Date and time with meter breaker status.
| ||||||||||||||||||||||||||||||
268.1204 | Datetime Euridis Communication Interface Status | Date and time with Euridis interface status.
| ||||||||||||||||||||||||||||||
268.1205 | Datetime PLC Status | Date and time with PLC status.
| ||||||||||||||||||||||||||||||
268.1206 | Datetime Peak Notice | Date and time with peak notice.
| ||||||||||||||||||||||||||||||
269.1200 | Datetime Tariff Activeenergy | Date and time with active energy per tariff.
| ||||||||||||||||||||||||||||||
270.1200 | Datetime Value Electric Current 3 | Date and time with current on the three phases.
| ||||||||||||||||||||||||||||||
270.1201 | Datetime Value Electric Potential 3 | Date and time with voltage on the three phases.
| ||||||||||||||||||||||||||||||
270.1202 | Datetime Value Apparentpower 3 | Date and time with apparent power on the three phases.
| ||||||||||||||||||||||||||||||
271.1200 | Tariffdayprofile | Daily tariff profile (tariff start time).
| ||||||||||||||||||||||||||||||
272.600 | Converter Info | Converter information: emergency level and DALI address.
| ||||||||||||||||||||||||||||||
273.001 | Forecast Temperature | Temperature forecast: value, probability and lead time.
| ||||||||||||||||||||||||||||||
273.002 | Forecast Windspeed | Wind speed forecast.
| ||||||||||||||||||||||||||||||
273.003 | Forecast Relativehumidity | Relative humidity forecast.
| ||||||||||||||||||||||||||||||
273.004 | Forecast Absolutehumidity | Absolute humidity forecast.
| ||||||||||||||||||||||||||||||
273.005 | Forecast CO2 | Forecast of CO₂.
| ||||||||||||||||||||||||||||||
273.006 | Forecast Airpollutants | Forecast of air pollutants.
| ||||||||||||||||||||||||||||||
273.007 | Forecast Sunintensity | Forecast of solar irradiance.
| ||||||||||||||||||||||||||||||
274.001 | Forecast Wind Direction | Forecast of wind direction.
| ||||||||||||||||||||||||||||||
276.1200 | ERL Status | Status of load management (duty cycles and update flags).
| ||||||||||||||||||||||||||||||
277.1200 | 4 Energyregisters | Group of 4 energy registers.
| ||||||||||||||||||||||||||||||
278.1200 | 5 Energyregisters | Group of 5 energy registers.
| ||||||||||||||||||||||||||||||
279.1200 | 6 Energyregisters | Group of 6 energy registers.
| ||||||||||||||||||||||||||||||
280.1200 | 11 Energyregisters | Group of 11 energy registers.
| ||||||||||||||||||||||||||||||
281.1200 | Datetime 4 Energyregisters | Date and time with 4 energy registers.
| ||||||||||||||||||||||||||||||
282.1200 | Datetime 5 Energyregisters | Date and time with 5 energy registers.
| ||||||||||||||||||||||||||||||
283.1200 | Datetime 6 Energyregisters | Date and time with 6 energy registers.
| ||||||||||||||||||||||||||||||
284.1200 | Datetime 11 Energyregisters | Date and time with 11 energy registers.
|