KNX Gateway: supported parameters and datatypes (DPT)

Parameters of the Ilevia Manager KNX gateway (X1 Plus or KNX/IP interface, KNX Secure) and all 453 supported KNX datatypes, with the components created for each one.

The Knx3 gateway is Ilevia Manager's next-generation KNX connection: it connects to the KNX bus directly from X1 Plus or via a KNX/IP interface, supports KNX Secure and recognizes 453 data types (DPT). For each DPT, Manager already knows which components to create, so a group object becomes a ready-to-use component in just a few clicks.

In short: 453 supported DPTs in 102 main types · KNX Secure with ETS keyring file · components automatically created from the DPT with the KNX Datapoint component.

Gateway parameters

Open Gateways, create a gateway (see Adding and removing a gateway) and choose Knx3 under Protocol.

Field

Initial value

Meaning

Type

X1 plus

X1 plus: uses the built-in KNX connection of X1 Plus, with no additional data. Custom: uses an external KNX/IP interface and shows the Ip Address and Port fields.

Ip Address

127.0.0.1

Only with Type = Custom: IP address of the KNX/IP interface.

Port

3671

Only with Type = Custom: port of the KNX/IP interface (3671 is the standard KNXnet/IP port).

KNX Individual Address

15.15.240

Required. Physical address used by the Ilevia server on the KNX bus. Use a free address from the ETS project; if the field is empty, it is highlighted in red.

Secure

off

Enables KNX Secure communication. It turns on automatically when you load a keyring file.

KNX Secure Keyring

no file

.knxkeys file exported from ETS. Click Choose File or drag the file onto the box: it is saved in the project and the text Keyring loaded appears.

Keyring Password

—

The password chosen in ETS when you exported the keyring. Manager checks it against the file: if it does not match, the field turns red.

The keyring file and its password provide access to the plant's secure communication: keep them confidential and update the keyring in Manager every time you re-export it from ETS.

KNX component parameters

In components connected to a Knx3 gateway, the KNX section contains these common fields:

Field

Meaning

Write address

Group address to which the component sends commands.

Feedback address

Group address from which the component reads the status (the actual actuator status).

Virtual feedback

If no status address exists, the component updates its own status with the value it sent.

Read bus value on startup

At startup, the server reads the current value from the bus, so the interface starts already updated.

Invert value

(Switch) Inverts the value: 1 becomes 0 and vice versa.

Group addresses have three levels (main/middle/sub, e.g. 1/2/3). Next to each address, a small menu lets you enable periodic sending (Send Interval, for write addresses) or periodic reading (Read Interval, for status addresses), with an interval in seconds: initial value 30 s, disabled.

Main component addresses

Some components have one address for each function, each with its own DPT:

Component

Functions and DPT

Switch

Command and status (DPT 1.001)

Pulse

Pulse (DPT 1.001)

Dimmer

On/Off (1.001) · Relative dimming (3.007) · Absolute dimming (5.001)

White light

On/Off (1.001) · Dimming (5.001) · Relative dimming (3.007) · Color temperature (7.600)

RGB light

On/Off (1.001) · White (5.001) · Dimming (5.001) · Relative dimming (3.007) · Color: RGB (3× 5.001), RGBW (4× 5.001), combined RGB (232.600), combined RGBW (251.600), HSV (5.003 + 2× 5.001), HSVW (5.003 + 3× 5.001)

Shutter

Up/Down (1.008, with Invert movement) · Position (5.001)

Thermostat

Setpoint (9.001) · Absolute offset (9.002) · Relative offset (6.010)

Climate thermostat

Setpoint (9.001) · Control mode (20.105) · Ventilation (5.001) · Heating/Cooling (1.100) · On/Off (1.001) · Humidity (9.007, status only)

Scenario

Scene control (18.001): scene number 0–63 and the Store current state into the scene (learn) option to save the scene

The KNX Datapoint component

For any other group object, use the KNX Datapoint component:

  1. Enter Write address and/or Feedback address.

  2. Choose the DPT from the list: you can search by number or by name (e.g. 9.001 - Value Temp).

  3. The Parameters table shows the DPT fields and the component that Manager will use for each one.

  4. Press Create components: Manager creates and links the components (Switch, Slider, Info, Thermostat…). Fields that are already linked are not duplicated.

Supported datatypes (DPT)

The Knx3 gateway recognizes 453 DPTs. The DPT number has two parts: the main type (before the dot) says how the value is represented on the bus (1 bit, 1 byte, floating point…), the subtype (after the dot) says what it represents and in which unit. For each group you find the format below, then for each DPT the meaning and, in the table under the description, the parameters: what each one contains and which component Manager creates for it with Create components.

In the KNX Datapoint component, the DPT parameters appear in the Parameters table with the same names (b, c, v, StepCode, FloatValue…).

DPT 1.x · 1 bit (on/off, true/false)

A single bit, field b: it is 0 or 1. The meaning of the two values changes according to the subtype.

DPT

Name

Meaning, values and parameters

1.001

Switch

On/off command or status. 0 = Off · 1 = On

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.002

Bool

Logical value. 0 = False · 1 = True

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.003

Enable

Enables a function. 0 = Disable · 1 = Enable

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.004

Ramp

Ramp (gradual change). 0 = No ramp · 1 = Ramp

Parameter

Meaning

Component

b

The 0/1 value (see above).

Pulse

1.005

Alarm

Alarm. 0 = No alarm · 1 = Alarm

Parameter

Meaning

Component

b

The 0/1 value (see above).

Alarm sensor

1.006

Binary value

Binary value (e.g. digital input). 0 = Low · 1 = High

Parameter

Meaning

Component

b

The 0/1 value (see above).

Contact

1.007

Step

Step. 0 = Decrease · 1 = Increase

Parameter

Meaning

Component

b

The 0/1 value (see above).

Pulse

1.008

Up/down

Shutter and blind movement. 0 = Up · 1 = Down

Parameter

Meaning

Component

b

The 0/1 value (see above).

Shutter

1.009

Open/close

Opening and closing. 0 = Open · 1 = Close

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.010

Start

Start and stop. 0 = Stop · 1 = Start

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.011

State

State of a function. 0 = Inactive · 1 = Active

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.012

Invert

Inversion. 0 = Not inverted · 1 = Inverted

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.013

Dim send style

Dimming transmission mode. 0 = Start/stop · 1 = Cyclic

Parameter

Meaning

Component

b

The 0/1 value (see above).

Info

1.014

Input source

Source of the value. 0 = Fixed · 1 = Calculated

Parameter

Meaning

Component

b

The 0/1 value (see above).

Info

1.015

Reset

Reset. 0 = No action · 1 = Reset

Parameter

Meaning

Component

b

The 0/1 value (see above).

Pulse

1.016

Ack

Acknowledge (e.g. of an alarm). 0 = No action · 1 = Acknowledge

Parameter

Meaning

Component

b

The 0/1 value (see above).

Pulse

1.017

Trigger

Trigger: both values start the same action.

Parameter

Meaning

Component

b

The 0/1 value (see above).

Pulse

1.018

Occupancy

Presence in a room. 0 = Unoccupied · 1 = Occupied

Parameter

Meaning

Component

b

The 0/1 value (see above).

Contact

1.019

Window Door

Window or door status. 0 = Closed · 1 = Open

Parameter

Meaning

Component

b

The 0/1 value (see above).

Contact

1.021

Logical Function

Logical function. 0 = OR · 1 = AND

Parameter

Meaning

Component

b

The 0/1 value (see above).

Info

1.022

Scene AB

Scene selection. 0 = Scene A · 1 = Scene B

Parameter

Meaning

Component

b

The 0/1 value (see above).

Scenario

1.023

Shutter blinds mode

Shutter control mode. 0 = Up/down only · 1 = Up/down + step/stop

Parameter

Meaning

Component

b

The 0/1 value (see above).

Shutter

1.024

Day/night

Day/night. 0 = Day · 1 = Night

Parameter

Meaning

Component

b

The 0/1 value (see above).

Info

1.100

Heat/cool

Heating or cooling. 0 = Cooling · 1 = Heating

Parameter

Meaning

Component

b

The 0/1 value (see above).

Climate thermostat

1.1200

Consumer/producer

Role in the energy system. 0 = Consumer · 1 = Producer

Parameter

Meaning

Component

b

The 0/1 value (see above).

Switch

1.1201

Energy direction

Direction of energy flow. 0 = Positive · 1 = Negative

Parameter

Meaning

Component

b

The 0/1 value (see above).

Power meter

DPT 2.x · 1 bit with priority (control)

Two bits. c (control): 0 = no priority, 1 = the value is forced with priority. v (value): the value, with the same meaning as the corresponding DPT 1.x.

DPT

Name

Meaning, values and parameters

2.001

Switch Control

As 1.001 with priority: v has the same values as 1.001, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.002

Bool Control

As 1.002 with priority: v has the same values as 1.002, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.003

Enable Control

As 1.003 with priority: v has the same values as 1.003, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.004

Ramp Control

As 1.004 with priority: v has the same values as 1.004, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Pulse

v

The 0/1 value, as in DPT 1.x.

Pulse

2.005

Alarm Control

As 1.005 with priority: v has the same values as 1.005, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Alarm sensor

v

The 0/1 value, as in DPT 1.x.

Alarm sensor

2.006

Binary value Control

As 1.006 with priority: v has the same values as 1.006, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Contact

v

The 0/1 value, as in DPT 1.x.

Contact

2.007

Step Control

As 1.007 with priority: v has the same values as 1.007, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Pulse

v

The 0/1 value, as in DPT 1.x.

Pulse

2.008

Direction1 Control

As 1.008 with priority: v has the same values as 1.008, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.009

Direction2 Control

As 1.009 with priority: v has the same values as 1.009, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.010

Start Control

As 1.010 with priority: v has the same values as 1.010, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.011

State Control

As 1.011 with priority: v has the same values as 1.011, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

2.012

Invert Control

As 1.012 with priority: v has the same values as 1.012, c = 1 forces the value.

Parameter

Meaning

Component

c

Priority: 0 = no, 1 = forced value.

Switch

v

The 0/1 value, as in DPT 1.x.

Switch

DPT 3.x · 4 bit: relative adjustment (dimming, blinds)

c: direction (3.007: 0 = decrease, 1 = increase · 3.008: 0 = up, 1 = down). StepCode: step size, 0 = stop; from 1 to 7 the step is 100 %, 50 %, 25 %, 12.5 %, 6.25 %, 3.13 %, 1.56 %.

DPT

Name

Meaning, values and parameters

3.007

Control Dimming

Relative dimming: increases or decreases brightness in steps.

Parameter

Meaning

Component

c

3.007: 0 = decrease, 1 = increase.

Info

StepCode

Step size: 0 = stop, 1–7 = 100 % … 1.56 %.

Info

3.008

Control Blinds

Relative step movement of blinds and curtains.

Parameter

Meaning

Component

c

0 = up, 1 = down.

Shutter

StepCode

Step size: 0 = stop, 1–7 = 100 % … 1.56 %.

Shutter

DPT 4.x · Character

One byte, field Character: a single character.

DPT

Name

Meaning, values and parameters

4.001

Char ASCII

An ASCII character.

Parameter

Meaning

Component

Character

The character.

Text entry

4.002

Char 8859 1

An ISO 8859-1 character (with accented letters).

Parameter

Meaning

Component

Character

The character.

Text entry

DPT 5.x · 8-bit unsigned

One byte, field UnsignedValue (0–255). The Manager converts it to the unit of the subtype (e.g. 0–100 % for 5.001).

DPT

Name

Meaning, values and parameters

5.001

Scaling

Percentage 0–100 % (e.g. brightness, position). The bus value ranges from 0 to 255.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Dimmer

5.003

Angle

Angle 0–360° (e.g. color hue).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

RGB light

5.004

Percent U8

Percentage 0–255 %.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Slider

5.005

Decimalfactor

Ratio or factor 0–255.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

5.006

Tariff

Active tariff (number 0–254).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Power meter

5.010

Value 1 Ucount

Pulse counter 0–255.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

DPT 6.x · 8-bit signed

One byte, field SignedValue (−128…127). DPT 6.020 instead uses fields a–e (status bits) and f (mode).

DPT

Name

Meaning, values and parameters

6.001

Percent V8

Signed percentage −128…127 %: the SignedValue field is used (the a–f fields shown in the list are only for 6.020).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Slider

a

Status bit A.

Slider

b

Status bit B.

Slider

c

Status bit C.

Slider

d

Status bit D.

Slider

e

Status bit E.

Slider

f

Active mode (0, 1 or 2).

Slider

6.010

Value 1 Count

Signed pulse counter −128…127.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

6.020

Status Mode3

Status with mode: fields a–e are five status bits, f indicates the active mode (0, 1 or 2).

Parameter

Meaning

Component

a

Status bit A.

Combo

b

Status bit B.

Combo

c

Status bit C.

Combo

d

Status bit D.

Combo

e

Status bit E.

Combo

f

Active mode (0, 1 or 2).

Combo

DPT 7.x · 2-byte unsigned

Two bytes, field UnsignedValue (0–65 535), in the unit of the subtype.

DPT

Name

Meaning, values and parameters

7.001

Value 2 Ucount

Pulse counter 0–65 535.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.002

Timeperiodmsec

Duration in milliseconds (0–65 535 ms).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.003

Timeperiod10msec

Duration in tens of milliseconds (0–655.35 s).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.004

Timeperiod100msec

Duration in hundreds of milliseconds (0–6 553.5 s).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.005

Timeperiodsec

Duration in seconds (0–65 535 s).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.006

Timeperiodmin

Duration in minutes (0–65 535 min).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.007

Timeperiodhrs

Duration in hours (0–65 535 h).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

7.010

Propdatatype

Identifier of the data type of a KNX property.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Combo

7.011

Length MM

Length in millimeters (0–65 535 mm).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

7.012

Ueicurrentma

Current in milliamperes (0–65 535 mA).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Power meter

7.013

Brightness

Brightness in lux (0–65 535 lx).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Dimmer

7.600

Absolute Colour Temperature

White light color temperature in kelvin (0–65 535 K, e.g. 2 700 K warm light).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

RGB light

DPT 8.x · signed 2 byte

Two bytes, SignedValue field (−32 768…32 767), in the unit of the subtype.

DPT

Name

Meaning, values and parameters

8.001

Value 2 Count

Signed pulse counter (−32 768…32 767).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.002

Deltatimemsec

Time difference in milliseconds (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.003

Deltatime10msec

Time difference in tenths of a millisecond (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.004

Deltatime100msec

Time difference in hundreds of milliseconds (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.005

Deltatimesec

Time difference in seconds (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.006

Deltatimemin

Time difference in minutes (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.007

Deltatimehrs

Time difference in hours (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

8.010

Percent V16

Signed percentage (−327.68…327.67 %).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Slider

8.011

Rotation Angle

Rotation angle in degrees (−32 768…32 767°).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

8.012

Length M

Length in meters (signed).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

DPT 9.x · 2 byte floating point (temperature, lux, speed…)

Two-byte KNX floating point, FloatValue field (from −671 088.64 to 670 760.96 with 0.01 precision). These are the DPTs most commonly used for sensor measurements.

DPT

Name

Meaning, values and parameters

9.001

Value Temp

Temperature in °C (e.g. room temperature, setpoint).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

9.002

Value Tempd

Temperature difference in K (e.g. setpoint offset).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

9.003

Value Tempa

Temperature change in K/h.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

9.004

Value Lux

Illuminance in lux.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

9.005

Value Wsp

Wind speed in m/s.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

9.006

Value Pres

Pressure in Pa.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

9.007

Value Humidity

Relative humidity in %.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Clima thermostat

9.008

Value Airquality

Air quality in ppm (e.g. CO₂).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

9.009

Value Airflow

Air flow rate in m³/h.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

9.010

Value Time1

Time in seconds.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Counter

9.011

Value Time2

Time in milliseconds.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Counter

9.020

Value Volt

Voltage in mV.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

9.021

Value Curr

Current in mA.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

9.022

Powerdensity

Power density in W/m² (e.g. solar irradiance).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

9.023

Kelvinperpercent

Coefficient in K/%.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

9.024

Power

Power in kW.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

9.025

Value Volume Flow

Flow rate in l/h.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

9.026

Rain Amount

Rainfall amount in l/m².

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

9.027

Value Temp F

Temperature in °F.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

9.028

Value Wsp Kmh

Wind speed in km/h.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

9.029

Value Absolute Humidity

Absolute humidity in g/m³.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Clima thermostat

9.030

Concentration µGM3

Concentration in µg/m³ (e.g. fine dust).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

DPT 10.x · Time of day

Fields Day (0 = no day, 1 = Monday … 7 = Sunday), Hour (0–23), Minutes (0–59), Seconds (0–59).

DPT

Name

Meaning, values and parameters

10.001

Timeofday

Time of day with day of week.

Parameter

Meaning

Component

Day

Day of the week: 0 = none, 1 = Monday … 7 = Sunday.

Time

Hour

Hour 0–23.

Time

Minutes

Minutes 0–59.

Time

Seconds

Seconds 0–59.

Time

DPT 11.x · Date

Fields Day (1–31), Month (1–12), Year (0–99: 90–99 = 1990–1999, 0–89 = 2000–2089).

DPT

Name

Meaning, values and parameters

11.001

Date

Date.

Parameter

Meaning

Component

Day

Day 1–31.

Date picker

Month

Month 1–12.

Date picker

Year

Year 0–99 (90–99 = 1990–1999, 0–89 = 2000–2089).

Date picker

DPT 12.x · 4-byte unsigned

Four bytes, UnsignedValue field (0–4 294 967 295), in the subtype unit.

DPT

Name

Meaning, values and parameters

12.001

Value 4 Ucont

Pulse counter 0–4 294 967 295.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

12.100

Longtimeperiod SEC

Long duration in seconds.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

12.101

Longtimeperiod MIN

Long duration in minutes.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

12.102

Longtimeperiod HRS

Long duration in hours.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

12.1200

Volumeliquid Litre

Liquid volume in liters.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

12.1201

Volume M3

Volume in m³.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

DPT 13.x · 4-byte signed (energy, counters)

Four bytes, SignedValue field (−2 147 483 648…2 147 483 647), in the subtype unit. These are the typical DPTs for energy counters.

DPT

Name

Meaning, values and parameters

13.001

Value 4 Count

Signed pulse counter (32-bit).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

13.002

Flowrate M3 H

Flow rate in m³/h (resolution 0.0001).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

13.010

Activeenergy

Active energy in Wh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.011

Apparantenergy

Apparent energy in VAh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.012

Reactiveenergy

Reactive energy in VARh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.013

Activeenergy KWH

Active energy in kWh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.014

Apparantenergy KVAH

Apparent energy in kVAh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.015

Reactiveenergy KVARH

Reactive energy in kVARh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.016

Activeenergy MWH

Active energy in MWh.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

13.017

Longdeltatimesec

Long time difference in seconds.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

13.1200

Deltavolumeliquid Litre

Change in liquid volume in liters.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

13.1201

Deltavolume M3

Change in volume in m³.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

DPT 14.x · 4-byte floating point (physical quantities)

Four-byte IEEE 754 floating point, FloatValue field, in the indicated International System unit.

DPT

Name

Meaning, values and parameters

14.000

Value Acceleration

Acceleration (m/s²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.001

Value Acceleration Angular

Angular acceleration (rad/s²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.002

Value Activation Energy

Activation energy (J/mol).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.003

Value Activity

Radioactive activity (1/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.004

Value Mol

Amount of substance (mol).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.005

Value Amplitude

Amplitude.

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.006

Value Anglerad

Angle (rad).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.007

Value Angledeg

Angle (°).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.008

Value Angular Momentum

Angular momentum (J·s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.009

Value Angular Velocity

Angular velocity (rad/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.010

Value Area

Area (m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.011

Value Capacitance

Capacitance (F).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.012

Value Charge Densitysurface

Surface charge density (C/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Text entry

14.013

Value Charge Densityvolume

Volume charge density (C/m³).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Text entry

14.014

Value Compressibility

Compressibility (m²/N).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.015

Value Conductance

Conductance (S).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.016

Value Electrical Conductivity

Electrical conductivity (S/m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.017

Value Density

Density (kg/m³).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.018

Value Electric Charge

Electric charge (C).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.019

Value Electric Current

Electric current (A).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.020

Value Electric Currentdensity

Current density (A/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.021

Value Electric Dipolemoment

Electric dipole moment (C·m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.022

Value Electric Displacement

Electric displacement (C/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.023

Value Electric Fieldstrenght

Electric field strength (V/m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.024

Value Electric Flux

Electric flux (V·m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.025

Value Electric Fluxdensity

Electric flux density (C/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.026

Value Electric Polarization

Electric polarization (C/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.027

Value Electric Potential

Electric potential (V).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.028

Value Electric Potentialdifference

Potential difference (V).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.029

Value Electromagneticmoment

Electromagnetic moment (A·m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.030

Value Electromotive Force

Electromotive force (V).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.031

Value Energy

Energy (J).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.032

Value Force

Force (N).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.033

Value Frequency

Frequency (Hz).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.034

Value Angular Frequency

Angular frequency (rad/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.035

Value Heat Capacity

Heat capacity (J/K).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.036

Value Heat Flowrate

Heat flow (W).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.037

Value Heat Quantity

Heat quantity (J).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.038

Value Impedance

Impedance (Ω).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.039

Value Length

Length (m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.040

Value Light Quantity

Light quantity (lm·s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.041

Value Luminance

Luminance (cd/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.042

Value Luminous Flux

Luminous flux (lm).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.043

Value Luminous Intensity

Luminous intensity (cd).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.044

Value Magnetic Fieldstrength

Magnetic field strength (A/m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.045

Value Magnetic Flux

Magnetic flux (Wb).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.046

Value Magnetic Fluxdensity

Magnetic flux density (T).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.047

Value Magnetic Moment

Magnetic moment (A·m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.048

Value Magnetic Polarization

Magnetic polarization (T).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.049

Value Magnetization

Magnetization (A/m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.050

Value Magnetomotiveforce

Magnetomotive force (A).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.051

Value Mass

Mass (kg).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.052

Value Massflux

Mass flow rate (kg/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.053

Value Momentum

Momentum (kg·m/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.054

Value Phase Anglerad

Phase angle (rad).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.055

Value Phase Angledeg

Phase angle (°).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.056

Value Power

Power (W).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.057

Value Power Factor

Power factor (cos φ).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.058

Value Pressure

Pressure (Pa).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.059

Value Reactance

Reactance (Ω).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.060

Value Resistance

Resistance (Ω).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.061

Value Resistivity

Resistivity (Ω·m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.062

Value Selfinductance

Inductance (H).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.063

Value Solidangle

Solid angle (sr).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.064

Value Sound Intensity

Sound intensity (W/m²).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.065

Value Speed

Speed (m/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.066

Value Stress

Mechanical stress (Pa).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.067

Value Surface Tension

Surface tension (N/m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.068

Value Common Temperature

Temperature (°C).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

14.069

Value Absolute Temperature

Absolute temperature (K).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

14.070

Value Temperaturedifference

Temperature difference (K).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Thermostat

14.071

Value Thermal Capacity

Thermal capacity (J/K).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.072

Value Thermal Conductivity

Thermal conductivity (W/(m·K)).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.073

Value Thermoelectricpower

Thermoelectric coefficient (V/K).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.074

Value Time

Time (s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Counter

14.075

Value Torque

Torque (N·m).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.076

Value Volume

Volume (m³).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.077

Value Volume Flux

Volume flow rate (m³/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.078

Value Weight

Weight (N).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.079

Value Work

Work (J).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Info

14.080

Value Apparentpower

Apparent power (VA).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Power meter

14.1200

Volume Flux Meter

Volume flow rate (m³/h).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

14.1201

Volume Flux LS

Volume flow rate (l/s).

Parameter

Meaning

Component

FloatValue

The value, in the unit indicated above.

Weather station

DPT 15.x · Access data

Fields D6–D1: the six digits of the code (0–9). E: read error (1 = error). P: permission (1 = access granted). D: read direction. C: encrypted code (1 = yes). Index: reader index (0–15).

DPT

Name

Meaning, values and parameters

15.000

Access Data

Access reader data (badge, code).

Parameter

Meaning

Component

D6

First digit of the code (0–9).

Info

D5

Second digit.

Info

D4

Third digit.

Info

D3

Fourth digit.

Info

D2

Fifth digit.

Info

D1

Sixth digit.

Info

E

Read error (1 = error).

Info

P

Permission (1 = access granted).

Info

D

Read direction (1 = right to left).

Info

C

Encrypted code (1 = yes).

Info

Index

Reader index 0–15.

Info

DPT 16.x · 14-character string

Field String: text up to 14 characters; unused characters are filled with zeros.

DPT

Name

Meaning, values and parameters

16.000

String ASCII

Text up to 14 ASCII characters.

Parameter

Meaning

Component

String

The text.

Text entry

16.001

String 8859 1

Text up to 14 ISO 8859-1 characters.

Parameter

Meaning

Component

String

The text.

Text entry

DPT 17.x · Scene number

Field SceneNumber: 0–63 (corresponds to scenes 1–64 usually indicated in ETS and on push buttons).

DPT

Name

Meaning, values and parameters

17.001

Scenenumber

Scene number to recall (0–63, on the display 1–64).

Parameter

Meaning

Component

SceneNumber

Scene number 0–63 (scenes 1–64).

Scenario

DPT 18.x · Scene control

SceneNumber: 0–63. C: 0 = recall the scene, 1 = store the current state in the scene (learn).

DPT

Name

Meaning, values and parameters

18.001

Scenecontrol

Recall or store a scene.

Parameter

Meaning

Component

SceneNumber

Scene number 0–63 (scene 1–64).

Scenario

C

0 = recall the scene, 1 = store (learn).

Scenario

DPT 19.x · Date and time

Fields Year (1900–2155), Month, DayOfMonth, DayOfWeek (0 = none, 1 = Monday … 7 = Sunday), HourOfDay (0–24), Minutes, Seconds, plus flags (1 = true): F fault · WD workday · NWD invalid workday · NY invalid year · ND invalid date · NDoW invalid day of week · NT invalid time · SUTI daylight saving time · CLQ clock synchronized with an external source · SRC synchronization reliability.

DPT

Name

Meaning, values and parameters

19.001

Datetime

Full date and time.

Parameter

Meaning

Component

Year

Year 1900–2155.

HourOfDay

Month

Month 1–12.

Date picker

DayOfMonth

Day of month 1–31.

Date picker

DayOfWeek

Day of week: 0 = none, 1 = Monday … 7 = Sunday.

Date picker

HourOfDay

Hour 0–24.

Date picker

Minutes

Minutes 0–59.

Date picker

Seconds

Seconds 0–59.

Date picker

F

Clock fault (1 = date/time not reliable).

Date picker

WD

Workday (1 = yes).

Date picker

NWD

1 = workday flag is not valid.

Date picker

NY

1 = year not valid.

Date picker

ND

1 = month and day not valid.

Date picker

NDoW

1 = day of week not valid.

Date picker

NT

1 = time not valid.

Date picker

SUTI

Daylight saving time (1 = yes).

Date picker

CLQ

Clock quality: 1 = synchronized with an external source.

Date picker

SRC

Synchronization source reliability.

Date picker

DPT 20.x · 8-bit enumeration (HVAC modes, states…)

One byte, field field1: a number corresponding to an entry in a list. The Combo component shows the entries with their name.

DPT

Name

Meaning, values and parameters

20.001

Sclomode

System mode (SCLO): 0 = autonomous · 1 = slave · 2 = master.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.002

Buildingmode

Building mode: 0 = in use · 1 = not in use · 2 = protection.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.003

Occmode

Occupancy: 0 = occupied · 1 = standby · 2 = unoccupied.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.004

Priority

Priority: 0 = high · 1 = medium · 2 = low · 3 = none.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.005

Lightapplicationmode

Lighting mode: 0 = normal · 1 = presence simulation · 2 = night round.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.006

Applicationarea

Application area (HVAC, lighting, security, blinds…) of a message or alarm.

Parameter

Meaning

Component

field1

The list entry number (see above).

Info

20.007

Alarmclasstype

Alarm class: 1 = simple · 2 = basic · 3 = extended.

Parameter

Meaning

Component

field1

The list entry number (see above).

Alarm sensor

20.008

Psumode

Power supply mode: 0 = off · 1 = on · 2 = automatic.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.011

Errorclass System

System error class (0 = no fault, then error type).

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.012

Errorclass HVAC

HVAC error class: 0 = no fault · 1 = sensor · 2 = control · 3 = actuator · 4 = other.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.013

Time Delay

Encoded delay: 0 = inactive, then from 1 s up to 24 h.

Parameter

Meaning

Component

field1

The list entry number (see above).

Counter

20.014

Beaufort Wind Force Scale

Wind force on the Beaufort scale (0–12).

Parameter

Meaning

Component

field1

The list entry number (see above).

Weather station

20.017

Sensorselect

Type of sensor connected to an input.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.020

Actuatorconnecttype

Actuator connection type: 1 = sensor · 2 = controller.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.021

Cloud Cover

Cloud cover in okta: 0 = clear … 8 = overcast · 9 = sky not visible.

Parameter

Meaning

Component

field1

The list entry number (see above).

Weather station

20.022

Powerreturnmode

Transmission after voltage return: 0 = do not send · 1 = always send · 2 = send if changed.

Parameter

Meaning

Component

field1

The list entry number (see above).

Power meter

20.100

Fueltype

Fuel: 0 = automatic · 1 = diesel · 2 = gas · 3 = solid.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.101

Burnertype

Burner: 1 = single-stage · 2 = two-stage · 3 = modulating.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.102

Hvacmode

HVAC mode: 0 = Auto · 1 = Comfort · 2 = Standby · 3 = Economy · 4 = Building protection.

Parameter

Meaning

Component

field1

The list entry number (see above).

Clima thermostat

20.103

Dhwmode

Domestic hot water mode: 0 = Auto · 1 = anti-legionella · 2 = normal · 3 = reduced · 4 = off/anti-freeze.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.104

Loadpriority

Load priority: 0 = none · 1 = shift · 2 = absolute.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.105

Hvaccontrmode

HVAC control mode: 0 = Auto · 1 = heating · 2 = morning preheating · 3 = cooling · 4 = night purge · 5 = pre-cooling · 6 = off · 7 = test · 8 = emergency heating · 9 = ventilation only · 10 = free cooling · 11 = ice · 12 = maximum heating · 13 = economy · 14 = dehumidification · 15 = calibration · 16 = emergency cooling · 17 = emergency steam · 20 = no request.

Parameter

Meaning

Component

field1

The list entry number (see above).

Clima thermostat

20.106

Hvacemergmode

Emergency mode: 0 = normal · 1 = pressurization · 2 = depressurization · 3 = purge · 4 = stop · 5 = fire.

Parameter

Meaning

Component

field1

The list entry number (see above).

Clima thermostat

20.107

Changeovermode

Seasonal changeover: 0 = Auto · 1 = cooling only · 2 = heating only.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.108

Valvemode

Valve mode (heating/cooling stages on/off or modulating).

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.109

Dampermode

Damper mode (outside air, supply air, return air…).

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.110

Heatermode

Heater mode (on/off or proportional stages).

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.111

Fanmode

Fan: 0 = stopped · 1 = always on · 2 = intermittently.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.112

Masterslavemode

Role: 0 = standalone · 1 = master · 2 = slave.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.113

Statusroomsetp

Setpoint in use: 0 = normal · 1 = alternative · 2 = building protection.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.114

Metering Devicetype

Meter type (electricity, gas, water, heat…).

Parameter

Meaning

Component

field1

The list entry number (see above).

Counter

20.115

Humdehummode

Humidification/dehumidification: 0 = inactive · 1 = humidify · 2 = dehumidify.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.120

Adatype

Air actuator type: 1 = damper · 2 = VAV.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.121

Backupmode

Backup behavior: 0 = fallback value · 1 = keeps last state.

Parameter

Meaning

Component

field1

The list entry number (see above).

Pulse

20.122

Startsynchronization

Start-up synchronization: 0 = position unchanged · 1 = close · 2 = open.

Parameter

Meaning

Component

field1

The list entry number (see above).

Switch

20.600

Behaviour Lock Unlock

Lock/unlock behavior (off, on, unchanged, stored value…).

Parameter

Meaning

Component

field1

The list entry number (see above).

Lock

20.601

Behaviour Bus Power Up Down

Behavior on bus voltage loss and restoration.

Parameter

Meaning

Component

field1

The list entry number (see above).

Power meter

20.602

DALI Fade Time

DALI fade time (code 0–15).

Parameter

Meaning

Component

field1

The list entry number (see above).

Counter

20.603

Blinkingmode

Blinking: 0 = disabled · 1 = without confirmation · 2 = with confirmation.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.604

Lightcontrolmode

Light control: 0 = automatic · 1 = manual.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.605

Switchpbmodel

Pushbutton model: 1 = single button · 2 = two buttons.

Parameter

Meaning

Component

field1

The list entry number (see above).

Switch

20.606

Pbaction

Pushbutton action: 0 = none · 1 = turn off · 2 = turn on · 3 = toggle on each press.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.607

Dimmpbmodel

Dimming pushbutton model (one or two buttons).

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.608

Switchonmode

Switch-on: 0 = last value · 1 = parameter value · 2 = last absolute value received.

Parameter

Meaning

Component

field1

The list entry number (see above).

Switch

20.609

Loadtypeset

Configured load type: 0 = automatic · 1 = leading-edge phase cut · 2 = trailing-edge phase cut.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.610

Loadtypedetected

Detected load type: 0 = undefined · 1 = leading-edge · 2 = trailing-edge · 3 = detection not possible.

Parameter

Meaning

Component

field1

The list entry number (see above).

Combo

20.611

Converter Test Control

DALI emergency converter test command (functional test, endurance test, stop…).

Parameter

Meaning

Component

field1

The list entry number (see above).

Info

20.612

Converter Control

DALI emergency converter command.

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.613

Converter Data Request

Data request to the DALI emergency converter.

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.801

Sabexceptbehaviour

Shutter behavior in case of exception (up, down, unchanged, stop…).

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.802

Sabbehaviour Lock Unlock

Shutter behavior when locking/unlocking.

Parameter

Meaning

Component

field1

The list item number (see above).

Lock

20.803

Sssbmode

Shutter control mode with push-buttons.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.804

Blindscontrolmode

Shutter control: 0 = automatic · 1 = manual.

Parameter

Meaning

Component

field1

The list item number (see above).

Shutter

20.1000

Commmode

Interface communication mode (data layer, bus monitor…).

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1001

Addinfotypes

Type of additional information in telegrams.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1002

RF Modeselect

KNX RF radio mode: 0 = asynchronous · 1 = BiBat master · 2 = BiBat slave.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1003

RF Filterselect

KNX RF radio filter (by domain address and/or serial number).

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1004

Medium

KNX medium: 0 = TP1 · 1 = PL110 · 2 = RF · 5 = KNX IP.

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.1005

PB Function

Push-button function.

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.1200

MBUS Breaker Valve State

M-Bus breaker/valve state: 0 = closed · 1 = open · 2 = unlocked.

Parameter

Meaning

Component

field1

The list item number (see above).

Switch

20.1202

Gas Measurement Condition

Gas measurement conditions: 0 = unknown · 1 = converted to temperature · 2 = base conditions · 3 = measurement conditions.

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.1203

Breaker Status

Meter breaker status: 0 = closed · then opened due to overload, overvoltage, load disconnection, command, overheating.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1204

Euridis Communication Interface Status

Euridis interface status: 0 = disabled · 1 = enabled.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1205

PLC Status

Meter PLC communication status.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1206

Peak Event Notice

Peak event notice (tariffs with peak days).

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.1207

Peak Event

Peak event in progress.

Parameter

Meaning

Component

field1

The list item number (see above).

Info

20.1208

TIC Type

Meter TIC output type (historical or standard).

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

20.1209

Type TIC Channel

TIC channel type.

Parameter

Meaning

Component

field1

The list item number (see above).

Combo

DPT 21.x · 8 bit bit set (statuses)

Fields b0–b7: eight independent bits, each one a status flag (1 = active).

DPT

Name

Meaning, values and parameters

21.001

Statusgen

General status: b0 out of service · b1 fault · b2 forced · b3 in alarm · b4 alarm not acknowledged.

Parameter

Meaning

Component

b0

Out of service (1 = yes).

Combo

b1

Fault (1 = yes).

Combo

b2

Forced (override) (1 = yes).

Combo

b3

In alarm (1 = yes).

Combo

b4

Alarm not acknowledged (1 = yes).

Combo

b5

Not used.

Combo

b6

Not used.

Combo

b7

Not used.

Combo

21.002

Device Control

Device control: b0 application stopped · b1 own address · b2 verify mode.

Parameter

Meaning

Component

b0

Application stopped by user (1 = yes).

Info

b1

Own individual address (1 = yes).

Info

b2

Verify mode active (1 = yes).

Info

b3

Not used.

Info

b4

Not used.

Info

b5

Not used.

Info

b6

Not used.

Info

b7

Not used.

Info

21.100

Forcesign

Heating override signal (request, protection, excess supply, domestic hot water, comfort…).

Parameter

Meaning

Component

b0

Forced request (1 = yes).

Info

b1

Protection (1 = yes).

Info

b2

Excess supply (1 = yes).

Info

b3

Overrun (1 = yes).

Info

b4

Normal domestic hot water (1 = yes).

Info

b5

Anti-legionella domestic hot water (1 = yes).

Info

b6

Space heating Comfort (1 = yes).

Info

b7

Space heating maximum (1 = yes).

Info

21.101

Forcesigncool

Cooling override signal: b0 forced request.

Parameter

Meaning

Component

b0

Forced request (1 = yes).

Info

b1

Not used.

Info

b2

Not used.

Info

b3

Not used.

Info

b4

Not used.

Info

b5

Not used.

Info

b6

Not used.

Info

b7

Not used.

Info

21.102

Statusrhc

Heating controller status: b0 fault · b1 eco · b2 supply limit · b3 return limit · b4 morning boost · b5/b6 start/stop optimization · b7 summer mode.

Parameter

Meaning

Component

b0

Fault (1 = yes).

Combo

b1

Eco active (1 = yes).

Combo

b2

Supply temperature limit (1 = yes).

Combo

b3

Return temperature limit (1 = yes).

Combo

b4

Morning boost (1 = yes).

Combo

b5

Start optimization (1 = yes).

Combo

b6

Stop optimization (1 = yes).

Combo

b7

Summer mode (1 = yes).

Combo

21.103

Statussdhwc

Solar domestic hot water status: b0 fault · b1 solar charging active · b2 sufficient solar energy.

Parameter

Meaning

Component

b0

Fault (1 = yes).

Combo

b1

Solar DHW charging active (1 = yes).

Combo

b2

Sufficient solar energy (1 = yes).

Combo

b3

Not used.

Combo

b4

Not used.

Combo

b5

Not used.

Combo

b6

Not used.

Combo

b7

Not used.

Combo

21.104

Fueltypeset

Available fuels: b0 diesel · b1 gas · b2 solid.

Parameter

Meaning

Component

b0

Diesel available (1 = yes).

Combo

b1

Gas available (1 = yes).

Combo

b2

Solid fuel available (1 = yes).

Combo

b3

Not used.

Combo

b4

Not used.

Combo

b5

Not used.

Combo

b6

Not used.

Combo

b7

Not used.

Combo

21.105

Statusrcc

Cooling controller status: b0 fault.

Parameter

Meaning

Component

b0

Fault (1 = yes).

Combo

b1

Not used.

Combo

b2

Not used.

Combo

b3

Not used.

Combo

b4

Not used.

Combo

b5

Not used.

Combo

b6

Not used.

Combo

b7

Not used.

Combo

21.106

Statusahu

Air handling unit status: b0 fault · b1 fan active · b2 heating · b3 cooling.

Parameter

Meaning

Component

b0

Fault (1 = yes).

Combo

b1

Fan active (1 = yes).

Combo

b2

Heating (1 = yes).

Combo

b3

Cooling (1 = yes).

Combo

b4

Not used.

Combo

b5

Not used.

Combo

b6

Not used.

Combo

b7

Not used.

Combo

21.601

Lightactuatorerrorinfo

Light actuator errors: load not detected, undervoltage, overcurrent, underload, faulty load, lamp failure, overheating.

Parameter

Meaning

Component

b0–b7

Status flags, one bit each (see above).

Info

21.1000

RF Modeinfo

Information on KNX RF radio mode.

Parameter

Meaning

Component

b0–b7

Status flags, one bit each (see above).

Combo

21.1001

RF Filterinfo

Information on the KNX RF radio filter.

Parameter

Meaning

Component

b0–b7

Status flags, one bit each (see above).

Info

21.1002

Security Report

Security report: b0 attack attempt detected.

Parameter

Meaning

Component

b0

Attack attempt detected (1 = yes).

Info

b1

Not used.

Info

b2

Not used.

Info

b3

Not used.

Info

b4

Not used.

Info

b5

Not used.

Info

b6

Not used.

Info

b7

Not used.

Info

21.1010

Channel Activation 8

Activation of 8 channels: b0–b7 = channels 1–8.

Parameter

Meaning

Component

b0–b7

One bit per channel (1 = active).

Info

21.1200

Virtualdrycontact

Virtual dry contacts: b0–b7 = contact status 1–8.

Parameter

Meaning

Component

b0–b7

Contact status 1–8.

Info

21.1201

Phases Status

Phase presence: b0 L1 · b1 L2 · b2 L3.

Parameter

Meaning

Component

b0

Phase L1 present (1 = yes).

Combo

b1

Phase L2 present (1 = yes).

Combo

b2

Phase L3 present (1 = yes).

Combo

b3

Not used.

Combo

b4

Not used.

Combo

b5

Not used.

Combo

b6

Not used.

Combo

b7

Not used.

Combo

DPT 22.x · 16-bit bit set

16-bit UnsignedValue field: each bit is a status flag.

DPT

Name

Meaning, values and parameters

22.100

Statusdhwc

Domestic hot water generator status (16 bits: fault, active charging, anti-legionella, solar energy…).

Parameter

Meaning

Component

UnsignedValue

16 status flags, one bit each.

Combo

22.101

Statusrhcc

Heating/cooling controller status (16 bits).

Parameter

Meaning

Component

UnsignedValue

16 status flags, one bit each.

Combo

22.1000

Media

Supported communication media (TP1, PL110, RF, IP).

Parameter

Meaning

Component

UnsignedValue

16 status flags, one bit each.

Info

22.1010

Channel Activation 16

Activation of 16 channels (one bit per channel).

Parameter

Meaning

Component

UnsignedValue

16 status flags, one bit each.

Info

DPT 23.x · 2-bit enumeration

Field s: a value from 0 to 3 with the specified meaning.

DPT

Name

Meaning, values and parameters

23.001

Onoffaction

On/off action: 0 = Off · 1 = On · 2 = Off/On · 3 = On/Off.

Parameter

Meaning

Component

s

Action value 0–3 (see above).

Combo

23.002

Alarm Reaction

Shutter alarm reaction: 0 = none · 1 = alarm position up · 2 = alarm position down.

Parameter

Meaning

Component

s

Action value 0–3 (see above).

Alarm sensor

23.003

Updown Action

Up/down action: 0 = Up · 1 = Down · 2 = Up/Down · 3 = Down/Up.

Parameter

Meaning

Component

s

Action value 0–3 (see above).

Shutter

23.102

HVAC PB Action

HVAC pushbutton action: 0 = Comfort/Economy · 1 = Comfort/none · 2 = Economy/none · 3 = Building protection/Auto.

Parameter

Meaning

Component

s

Action value 0–3 (see above).

Combo

DPT 24.x · Variable-length string

Field String: variable-length text.

DPT

Name

Meaning, values and parameters

24.001

Varstring 8859 1

Variable-length ISO 8859-1 text.

Parameter

Meaning

Component

String

The text.

Text entry

DPT 25.x · Double nibble

Fields Busy and Nak: two counters from 0 to 15.

DPT

Name

Meaning, values and parameters

25.1000

Doublenibble

Double repetition counter (Busy and Nak, 0–15 each).

Parameter

Meaning

Component

Busy

Number of repetitions for bus busy (0–15).

Info

Nak

Number of repetitions for no acknowledgement (0–15).

Info

DPT 26.x · Scene information

SceneNumber: 0–63. B: 0 = active scene, 1 = inactive scene.

DPT

Name

Meaning, values and parameters

26.001

Sceneinfo

Scene information: number and active/inactive status.

Parameter

Meaning

Component

B

0 = active scene, 1 = inactive.

Scenario

SceneNumber

Scene number 0–63 (scenes 1–64).

Scenario

DPT 27.x · Combined on/off states

Fields s0–s15: on/off status of outputs 1–16. m0–m15: mask, 1 = the status of the corresponding output is valid.

DPT

Name

Meaning, values and parameters

27.001

Combinedinfoonoff

On/off status of 16 outputs in a single telegram, with validity mask.

Parameter

Meaning

Component

s0–s15

On/off status of the outputs (1 = on).

Info

m0–m15

Mask: 1 = the status of the corresponding output is valid.

Info

DPT 28.x · Unicode string (UTF-8)

Field String: variable-length UTF-8 text (accepts any language).

DPT

Name

Meaning, values and parameters

28.001

Uft 8

Variable-length UTF-8 text.

Parameter

Meaning

Component

String

The text.

Info

DPT 29.x · 8-byte signed value (V64 energy)

Eight bytes, field SignedValue: energy counters of large plants.

DPT

Name

Meaning, values and parameters

29.010

Activeenergy V64

Active energy in Wh (64-bit, for large-plant meters).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

29.011

Apparantenergy V64

Apparent energy in VAh (64-bit).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

29.012

Reactiveenergy V64

Reactive energy in VARh (64-bit).

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Power meter

DPT 30.x · 24-channel activation

Fields b0–b23: one bit for each of the 24 channels.

DPT

Name

Meaning, values and parameters

30.1010

Channel Activation 24

Activation of 24 channels (one bit per channel).

Parameter

Meaning

Component

b0–b23

One bit per channel (1 = active).

Info

DPT 31.x · Extended HVAC push-button actions

Field s: the push-button action on HVAC modes.

DPT

Name

Meaning, values and parameters

31.101

PB Action HVAC Extended

Extended HVAC push-button action (Comfort, Standby, Economy, Building protection modes).

Parameter

Meaning

Component

s

Action value 0–3 (see above).

Combo

DPT 200–284 · Composite types (HVAC, meters, DALI, colors, energy…)

147 DPT. These DPTs carry multiple values in the same telegram: the Manager creates one component for each field. Field names often repeat:

Field

Meaning

Value / UnsignedValue / SignedValue

The main value, in the DPT unit.

StatusCommand

Status byte accompanying the value (fault, out of service, forced, alarm…). DPTs with «Z» in the name have this field.

Attributes

Flags describing the value (validity, source, limits).

Mode / DelayTime

The next mode and how many minutes until it becomes active.

TempSetp…

Setpoint (or setpoint shift) for Comfort, Standby, Economy, Building protection.

R, G, B, W · MR, MG, MB, MW

Color components 0–255 and related validity masks.

C… / StepCode…

Direction and size of the step in relative adjustments (as in DPT 3.x).

Year … Seconds, F

Date and time with quality flag (as in DPT 19.001).

Phase1, Phase2, Phase3

Value on each of the three phases.

Mask, Probability

In forecasts: which fields are valid and the probability (%).

DPT

Name

Meaning, values and parameters

200.100

Heatcool Z

Heating/cooling with status byte.

Parameter

Meaning

Component

b

The 0/1 value (see above).

Clima thermostat

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Clima thermostat

200.101

Binaryvalue Z

Binary value with status byte.

Parameter

Meaning

Component

b

The 0/1 value (see above).

Info

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Info

201.100

Hvacmode Z

HVAC mode (as 20.102) with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Clima thermostat

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Clima thermostat

201.102

Dhwmode Z

Domestic hot water mode (as 20.103) with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Combo

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Combo

201.104

Hvaccontrmode Z

HVAC control mode (as 20.105) with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Clima thermostat

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Clima thermostat

201.105

Enablehc Stage Z

Enabling of heating/cooling stages with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Switch

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Switch

201.107

Buildingmode Z

Building mode (as 20.002) with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Combo

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Combo

201.108

Occmode Z

Occupancy (as 20.003) with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Combo

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Combo

201.109

Hvacemergmode Z

HVAC emergency mode (as 20.106) with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Clima thermostat

StatusCommand

Status byte of the value: fault, out of service, forced, alarm.

Clima thermostat

202.001

Relvalue Z

Relative value 0–255 with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Info

202.002

Ucountvalue8 Z

Counter 0–255 with status byte.

Parameter

Meaning

Component

Value

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.002

Timeperiodmsec Z

Duration in ms with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.003

Timeperiod10msec Z

Duration in tenths of ms with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.004

Timeperiod100msec Z

Duration in hundreds of ms with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.005

Timeperiodsec Z

Duration in seconds with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.006

Timeperiodmin Z

Duration in minutes with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.007

Timeperiodhrs Z

Duration in hours with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.011

Uflowrateliter H Z

Flow rate in l/h with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Info

203.012

Ucountvalue16 Z

Counter 0–65 535 with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

203.013

Ueicurrentµa Z

Current in µA with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Power meter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Power meter

203.014

Powerkw Z

Power in kW with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Power meter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Power meter

203.015

Atmpressureabs Z

Absolute atmospheric pressure with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Weather station

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Weather station

203.017

Percentu16 Z

Percentage with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Slider

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Slider

203.100

Hvacairqual Z

Air quality in ppm with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Info

203.101

Windspeed Z

Wind speed with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Weather station

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Weather station

203.102

Sunintensity Z

Solar irradiance with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Weather station

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Weather station

203.104

Hvacairflowabs Z

Absolute air flow with status byte.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Weather station

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Weather station

204.001

Relsignedvalue Z

Relative signed value with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Info

205.002

Deltatimemsec Z

Time difference in ms with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

205.003

Deltatime10msec Z

Time difference in tenths of ms with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

205.004

Deltatime100msec Z

Time difference in hundreds of ms with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, alarmed.

Counter

205.005

Deltatimesec Z

Time difference in seconds with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Counter

205.006

Deltatimemin Z

Time difference in minutes with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Counter

205.007

Deltatimehrs Z

Time difference in hours with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Counter

205.017

Percent V16 Z

Signed percentage with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Slider

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Slider

205.100

Temphvacabs Z

Absolute HVAC temperature (°C) with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Thermostat

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Thermostat

205.101

Temphvacrel Z

Relative HVAC temperature (K) with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Thermostat

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Thermostat

205.102

Hvacairflowrel Z

Relative air flow rate with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Weather station

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Weather station

205.103

Hvacairqualrel Z

Relative air quality with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Info

206.100

Hvacmodenext

Next HVAC mode and in how many minutes it will activate.

Parameter

Meaning

Component

UnsignedValue

In how many minutes the next mode activates.

Clima thermostat

Mode

The next mode that will activate.

Clima thermostat

206.102

Dwhmodenext

Next domestic hot water mode and in how many minutes.

Parameter

Meaning

Component

UnsignedValue

In how many minutes the next mode activates.

Combo

Mode

The next mode that will activate.

Combo

206.104

Occmodenext

Next occupancy and in how many minutes.

Parameter

Meaning

Component

UnsignedValue

In how many minutes the next mode activates.

Combo

Mode

The next mode that will activate.

Combo

206.105

Buildingmodenext

Next building mode and in how many minutes.

Parameter

Meaning

Component

UnsignedValue

In how many minutes the next mode activates.

Combo

Mode

The next mode that will activate.

Combo

207.100

Statusbuc

Burner/boiler status.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Combo

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Combo

207.101

Locksign

Lock signal (lock request).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Lock

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Lock

207.102

Valuedemboc

Boiler power request (%).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Info

207.104

Actposdemabs

Requested actuator position (%).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Info

207.105

Statusact

Actuator status.

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Combo

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Combo

207.600

Statuslightingactuator

Lighting actuator status (level and flag).

Parameter

Meaning

Component

UnsignedValue

The value, in the unit indicated above.

Combo

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Combo

209.100

Statushpm

Heat producer status: temperature and attributes.

Parameter

Meaning

Component

SignedValue

Temperature (°C).

Combo

Attributes

Flags that qualify the value (validity, fault, limits).

Combo

209.101

Temproomdemabs

Requested room temperature and attributes.

Parameter

Meaning

Component

SignedValue

Temperature (°C).

Thermostat

Attributes

Flags that qualify the value (validity, fault, limits).

Thermostat

209.102

Statuscpm

Cold producer status: temperature and attributes.

Parameter

Meaning

Component

SignedValue

Temperature (°C).

Combo

Attributes

Flags that qualify the value (validity, fault, limits).

Combo

209.103

Statuswtc

Water temperature controller status.

Parameter

Meaning

Component

SignedValue

Temperature (°C).

Combo

Attributes

Flags that qualify the value (validity, fault, limits).

Combo

210.100

Tempflowwaterdemabs

Requested supply water temperature, with attributes.

Parameter

Meaning

Component

SignedValue

Temperature (°C).

Thermostat

Attributes

Flags that qualify the value (validity, fault, limits).

Thermostat

211.100

Energydemwater

Energy request for water and active control mode.

Parameter

Meaning

Component

UnsignedValue

Energy request (%).

Power meter

ContrModeAct

Active control mode.

Power meter

212.100

Temproomsetpsetshift 3

Room setpoint offsets for Comfort, Standby and Economy.

Parameter

Meaning

Component

TempSetpShiftComf

Comfort setpoint shift (K).

Thermostat

TempSetpShiftStdby

Standby setpoint shift (K).

Thermostat

TempSetpShiftEco

Economy setpoint shift (K).

Thermostat

212.101

Temproomsetpset 3

Room setpoints Comfort, Standby and Economy.

Parameter

Meaning

Component

TempSetpShiftComf

Comfort setpoint (°C).

Thermostat

TempSetpShiftStdby

Standby setpoint (°C).

Thermostat

TempSetpShiftEco

Economy setpoint (°C).

Thermostat

213.100

Temproomsetpset 4

Four room setpoints: Comfort, Standby, Economy, Building protection.

Parameter

Meaning

Component

TempSetpShiftComf

Comfort setpoint (°C).

Thermostat

TempSetpShiftStdby

Standby setpoint (°C).

Thermostat

TempSetpEco

Economy setpoint (°C).

Thermostat

TempSetpBProt

Building protection setpoint (°C).

Thermostat

213.101

Tempdhwsetpset 4

Four domestic hot water setpoints.

Parameter

Meaning

Component

TempSetpShiftComf

Comfort setpoint (°C).

Thermostat

TempSetpShiftStdby

Standby setpoint (°C).

Thermostat

TempSetpEco

Economy setpoint (°C).

Thermostat

TempSetpBProt

Building protection setpoint (°C).

Thermostat

213.102

Temproomsetpsetshift 4

Four room setpoint shifts.

Parameter

Meaning

Component

TempSetpShiftComf

Comfort setpoint shift (K).

Thermostat

TempSetpShiftStdby

Standby setpoint shift (K).

Thermostat

TempSetpEco

Economy setpoint shift (K).

Thermostat

TempSetpBProt

Building protection setpoint shift (K).

Thermostat

214.100

Powerflowwaterdemhpc

Request to the heat generator: supply temperature, relative power limit and attributes.

Parameter

Meaning

Component

TempFlowDem

Requested supply temperature (°C).

Power meter

RelDemLimit

Requested power limit (%).

Power meter

Attributes

Flags that qualify the value (validity, fault, limits).

Power meter

214.101

Powerflowwaterdemcpm

Request to the cooling generator: supply temperature, relative power limit and attributes.

Parameter

Meaning

Component

TempFlowDem

Requested supply temperature (°C).

Power meter

RelDemLimit

Requested power limit (%).

Power meter

Attributes

Flags that qualify the value (validity, fault, limits).

Power meter

215.100

Statusboc

Boiler status: temperature, attributes and relative power.

Parameter

Meaning

Component

Temp

Temperature (°C).

Combo

Attributes

Flags that qualify the value (validity, fault, limits).

Combo

Prel

Relative power (%).

Combo

215.101

Statuscc

Chiller status: temperature, attributes and relative power.

Parameter

Meaning

Component

Temp

Temperature (°C).

Combo

Attributes

Flags that qualify the value (validity, fault, limits).

Combo

Prel

Relative power (%).

Combo

216.100

Specheatprod

Heat generator characteristics: rated power, stages, burner type and fuel type.

Parameter

Meaning

Component

Pnom

Rated power (kW).

Info

BstageLimit

Burner stage limit.

Info

BurnerType

Burner type (as 20.101).

Info

FuelType

Fuel type (as 20.100).

Info

217.001

Version

Version: magic number, version and revision.

Parameter

Meaning

Component

MagicNumber

Format identification number.

Counter

VersionNumber

Version number.

Counter

RevisionNumber

Revision number.

Counter

218.001

Volumeliter Z

Volume in liters with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Info

218.002

Flowrate M3 H Z

Flow rate in m³/h with status byte.

Parameter

Meaning

Component

SignedValue

The value, in the unit indicated above.

Info

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Info

219.001

Alarminfo

Alarm information: record number, priority, application area, error class and alarm states.

Parameter

Meaning

Component

LogNumber

Alarm record number.

Alarm sensor

AlarmPriority

Alarm priority (as 20.004).

Alarm sensor

ApplicationArea

Application area (as 20.006).

Alarm sensor

ErrorClass

Error class (as 20.011 / 20.012).

Alarm sensor

Attributes

Flags that qualify the value (validity, fault, limits).

Alarm sensor

AlarmStatusAttributes

Alarm status: active, unacknowledged, blocked.

Alarm sensor

220.100

Temphvacabsnext

Next HVAC temperature and when it will be activated.

Parameter

Meaning

Component

DelayTime

In how many minutes the change will occur.

Thermostat

Temp

Temperature (°C).

Thermostat

221.001

Sernum

KNX serial number: manufacturer code and sequential number.

Parameter

Meaning

Component

ManifacturerCode

KNX manufacturer code.

Counter

IncrementedNumber

Sequential device number.

Counter

222.100

Temproomsetpsetf16 3

Floating-point Comfort, Standby and Economy setpoints.

Parameter

Meaning

Component

TempSetpComf

Comfort setpoint (°C).

Thermostat

TempSetpStdby

Standby setpoint (°C).

Thermostat

TempSetpEco

Economy setpoint (°C).

Thermostat

222.101

Temproomsetpsetshiftf16 3

Floating-point Comfort, Standby and Economy setpoint shifts.

Parameter

Meaning

Component

TempSetpShiftComf

Comfort setpoint shift (K).

Thermostat

TempSetpShiftStdby

Standby setpoint shift (K).

Thermostat

TempSetpShiftEco

Economy setpoint shift (K).

Thermostat

223.100

Energydemair

Energy demand for air, emergency mode and control mode.

Parameter

Meaning

Component

EnergyDem

Energy demand (%).

Power meter

HVACEmergMode

Emergency mode (as 20.106).

Power meter

HVACContrMod

Control mode (as 20.105).

Power meter

224.100

Tempsupplyairsetpset

Supply air setpoint in cooling and heating, with modes.

Parameter

Meaning

Component

TempSetpCooling

Cooling air setpoint (°C).

Thermostat

TempSetpHeating

Heating air setpoint (°C).

Thermostat

HVACEmergMode

Emergency mode (as 20.106).

Thermostat

HVACContrMod

Control mode (as 20.105).

Thermostat

225.001

Scalingspeed

Rate of change: time and percentage.

Parameter

Meaning

Component

UnsignedValue

Change time.

Slider

Percent

Change percentage.

Slider

225.002

Scaling Stept Time

Step time of the change and percentage.

Parameter

Meaning

Component

UnsignedValue

Time of each step.

Slider

Percent

Change percentage.

Slider

225.003

Tariffnext

Next tariff and when it will be activated.

Parameter

Meaning

Component

UnsignedValue

In how many minutes the next tariff will be activated.

Power meter

Percent

Number of the next tariff.

Power meter

229.001

Meteringvalue

Value of a counter with status and quantity type (unit).

Parameter

Meaning

Component

SignedValue

Counter value.

Counter

StatusCommand

Status byte of the value: fault, out of service, forced, in alarm.

Counter

ValInfField

Quantity type and value unit (M-Bus code).

Counter

230.1000

MBUS Address

M-Bus address: manufacturer, identification number, version and medium.

Parameter

Meaning

Component

ManufactID

M-Bus manufacturer code.

Info

IdentNumber

Identification number.

Info

Version

Device version.

Info

Medium

Measured medium (electricity, gas, water, heat…).

Info

231.001

ASCII Locale

Language and region (two letters each).

Parameter

Meaning

Component

Language

Two-letter language code.

Text entry

Region

Two-letter region code.

Text entry

232.600

Colour RGB

RGB color: red, green, blue 0–255.

Parameter

Meaning

Component

R

Red 0–255.

RGB light

G

Green 0–255.

RGB light

B

Blue 0–255.

RGB light

234.001

Languagecodealpha2 ASCII

Two-letter language code (ISO 639-1, e.g. it).

Parameter

Meaning

Component

Characters

The two characters of the code.

Text entry

234.002

Regioncodealpha2 ASCII

Two-letter region code (ISO 3166-1, e.g. IT).

Parameter

Meaning

Component

Characters

The two characters of the code.

Text entry

235.001

Tariff Activeenergy

Active energy by tariff: value, tariff number and validity.

Parameter

Meaning

Component

SignedValue

Active energy (Wh).

Power meter

Tariff

Tariff number.

Power meter

Validity

Validity of the value and tariff.

Power meter

236.001

Prioritised Mode Control

Priority mode control: disable, priority and mode.

Parameter

Meaning

Component

d

1 = disables priority control.

Combo

p

Priority level.

Combo

m

Requested mode.

Combo

237.600

DALI Control Gear Diagnostic

DALI control gear diagnostics: errors of the converter, ballast and lamp, with address.

Parameter

Meaning

Component

CE

Converter error.

Info

BF

Ballast fault.

Info

LF

Lamp fault.

Info

RR

Request or response.

Info

AI

Indicates whether Addr is a single address or a group address.

Info

Addr

DALI address.

Info

238.001

Sceneconfig

Scene configuration: number and storage and activation options.

Parameter

Meaning

Component

S

Scene storage option.

Scenario

SA

Scene activation (1 = not active).

Scenario

SN

Scene number.

Scenario

238.600

DALI Diagnostic

DALI diagnostics (status and address).

Parameter

Meaning

Component

S

Scene storage option.

Info

SA

Scene activation (1 = not active).

Info

SN

Scene number.

Info

239.001

Flaggedscaling

Percentage with validity flag.

Parameter

Meaning

Component

CA

Value validity (1 = valid).

Slider

SetValue

Percentage 0–100 %.

Slider

240.800

Combinedposition

Combined position of blinds with slats: height %, slat tilt % and validity.

Parameter

Meaning

Component

HeightPosition

Height position (%).

Shutter

SlatsPosition

Slat tilt (%).

Shutter

Attributes

Flags that qualify the value (validity, fault, limits).

Shutter

241.800

Statussab

Complete status of blinds/sunshades: height, slats and flags (limit switches, obstacle, override, wind/rain alarms…).

Parameter

Meaning

Component

HeightPosition

Height position (%).

Combo

SlatsPosition

Slat tilt (%).

Combo

a–p

Status flags: upper/lower limit switch, obstacle, override, wind/rain/frost alarms, movement in progress…

Combo

242.600

Colour XYY

Color in the xyY space: x and y coordinates, brightness and validity flag.

Parameter

Meaning

Component

XAxis

Color x coordinate.

RGB light

YAxis

Color y coordinate.

RGB light

Brightness

Brightness (%).

RGB light

C

1 = valid color coordinates.

RGB light

B

1 = valid brightness.

RGB light

243.600

Colour Transition XYY

xyY color transition with time.

Parameter

Meaning

Component

TimePeriod

Transition time.

RGB light

XAxis

Color x coordinate.

RGB light

YAxis

Color y coordinate.

RGB light

Brightness

Brightness (%).

RGB light

C

1 = valid color coordinates.

RGB light

B

1 = valid brightness.

RGB light

244.600

Converter Status

Status of the DALI emergency converter (mode, pending test, faults).

Parameter

Meaning

Component

CM

Converter mode.

Combo

HS

Hardware status.

Combo

FP

Functional test pending.

Combo

DP

Duration test pending.

Combo

PP

Partial test pending.

Combo

CF

Converter fault.

Combo

245.600

Converter Test Result

Emergency DALI converter test result.

Parameter

Meaning

Component

LTRF

Result of the last functional test.

Info

LTRD

Result of the last duration test.

Info

LTRP

Result of the last partial test.

Info

SF

How the functional test was started.

Info

SD

How the duration test was started.

Info

SP

How the partial test was started.

Info

LDTR

Measured battery duration during the test.

Info

LPDTR

Measured charge level during the partial test.

Info

246.600

Battery Info

Battery status and charge level.

Parameter

Meaning

Component

BS

Battery status.

Info

BCL

Battery charge level (%).

Info

247.600

Converter Test Info

Information on the emergency converter test (date and durations).

Parameter

Meaning

Component

DateTime

Test date and time.

Info

TimePeriodSec

Duration in seconds.

Info

TimePeriodHrs

Duration in hours.

Info

248.600

Converter Info Fix

Fixed emergency converter characteristics (levels, rated duration).

Parameter

Meaning

Component

InfoValid

Information validity.

Info

EmMinLevel

Minimum emergency level.

Info

EmMaxLevel

Maximum emergency level.

Info

RatedDur

Rated emergency duration.

Info

GearFeat

Device features.

Info

249.600

Brightness Colour Temperature Transition

Brightness and color temperature transition.

Parameter

Meaning

Component

Masks

Mask: which telegram values are valid.

RGB light

251.600

Colour RGBW

RGBW color: red, green, blue, white 0–255 and validity masks.

Parameter

Meaning

Component

R

Red 0–255.

RGB light

G

Green 0–255.

RGB light

B

Blue 0–255.

RGB light

W

White 0–255.

RGB light

MR

1 = the red value is valid.

RGB light

MG

1 = the green value is valid.

RGB light

MB

1 = the blue value is valid.

RGB light

MW

1 = the white value is valid.

RGB light

252.600

Relative Control RGBW

Relative RGBW control: direction and step for each color.

Parameter

Meaning

Component

CR

Red direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourRed

Red step (0 = stop).

RGB light

CG

Green direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourGreen

Green step (0 = stop).

RGB light

CB

Blue direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourBlue

Blue step (0 = stop).

RGB light

CW

White direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourWhite

White step (0 = stop).

RGB light

Masks

Mask: which telegram values are valid.

RGB light

253.600

Relative Control XYY

Relative xyY control: saturation, color, and brightness.

Parameter

Meaning

Component

CS

Saturation direction: 0 = decrease, 1 = increase.

RGB light

StepCodeSaturation

Saturation step (0 = stop).

RGB light

CC

Color direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColour

Color step (0 = stop).

RGB light

CB

Brightness direction: 0 = decrease, 1 = increase.

RGB light

StepCodeBrightness

Brightness step (0 = stop).

RGB light

Masks

Mask: which telegram values are valid.

RGB light

254.600

Relative Control RGB

Relative RGB control: direction and step for each color.

Parameter

Meaning

Component

CR

Red direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourRed

Red step (0 = stop).

RGB light

CG

Green direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourGreen

Green step (0 = stop).

RGB light

CB

Blue direction: 0 = decrease, 1 = increase.

RGB light

StepCodeColourBlue

Blue step (0 = stop).

RGB light

255.001

Geographicallocation

Geographic location: longitude and latitude.

Parameter

Meaning

Component

Longitude

Longitude (°).

Info

Latitude

Latitude (°).

Info

256.001

Datetime Period

Period with start and end date and time.

Parameter

Meaning

Component

start

Start date and time.

Date picker

stop

End date and time.

Date picker

257.1200

Value Electric Current 3

Current on the three phases.

Parameter

Meaning

Component

Phase1

Value on phase L1.

Power meter

Phase2

Value on phase L2.

Power meter

Phase3

Value on phase L3.

Power meter

257.1201

Value Electric Potential 3

Voltage on the three phases.

Parameter

Meaning

Component

Phase1

Value on phase L1.

Power meter

Phase2

Value on phase L2.

Power meter

Phase3

Value on phase L3.

Power meter

257.1202

Value Apparentpower 3

Apparent power on the three phases.

Parameter

Meaning

Component

Phase1

Value on phase L1.

Power meter

Phase2

Value on phase L2.

Power meter

Phase3

Value on phase L3.

Power meter

265.001

Datetime Switch

Date and time with on/off value.

Parameter

Meaning

Component

Year … SRC

Date, time, and quality flag, as in DPT 19.001.

Date picker

b

0/1 value linked to the date (see above).

Date picker

265.005

Datetime Alarm

Date and time with alarm.

Parameter

Meaning

Component

Year … SRC

Date, time, and quality flag, as in DPT 19.001.

Alarm sensor

b

0/1 value linked to the date (see above).

Alarm sensor

265.009

Datetime Openclose

Date and time with open/close.

Parameter

Meaning

Component

Year … SRC

Date, time, and quality flag, as in DPT 19.001.

Date picker

b

0/1 value linked to the date (see above).

Date picker

265.011

Datetime State

Date and time with active/inactive state.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

b

The 0/1 value linked to the date (see above).

Date picker

265.012

Datetime Invert

Date and time with inversion.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

b

The 0/1 value linked to the date (see above).

Date picker

265.1200

Datetime Consumerproducer

Date and time with consumer/producer.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

b

The 0/1 value linked to the date (see above).

Date picker

265.1201

Datetime Energydirection

Date and time with energy direction.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

b

The 0/1 value linked to the date (see above).

Power meter

266.027

Datetime Value Electric Potential

Date and time with voltage.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

FloatValue

The value, in the unit indicated above.

Power meter

266.056

Datetime Value Power

Date and time with power.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

FloatValue

The value, in the unit indicated above.

Power meter

266.080

Datetime Value Apparentpower

Date and time with apparent power.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

FloatValue

The value, in the unit indicated above.

Power meter

267.001

Datetime UTF 8

Date and time with UTF-8 text.

Parameter

Meaning

Component

date

Date and time.

Date picker

utf

UTF-8 text.

Date picker

268.1203

Datetime Breaker Status

Date and time with meter breaker status.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

field1

The list item number (see above).

Date picker

268.1204

Datetime Euridis Communication Interface Status

Date and time with Euridis interface status.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

field1

The list item number (see above).

Date picker

268.1205

Datetime PLC Status

Date and time with PLC status.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

field1

The list item number (see above).

Date picker

268.1206

Datetime Peak Notice

Date and time with peak notice.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Date picker

field1

The list item number (see above).

Date picker

269.1200

Datetime Tariff Activeenergy

Date and time with active energy per tariff.

Parameter

Meaning

Component

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

ActiveElectricalEnergy

Active energy (Wh).

Power meter

Tariff

Tariff number.

Power meter

Validity

Validity of the value and the tariff.

Power meter

270.1200

Datetime Value Electric Current 3

Date and time with current on the three phases.

Parameter

Meaning

Component

Phase1

Value on phase L1.

Power meter

Phase2

Value on phase L2.

Power meter

Phase3

Value on phase L3.

Power meter

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

270.1201

Datetime Value Electric Potential 3

Date and time with voltage on the three phases.

Parameter

Meaning

Component

Phase1

Value on phase L1.

Power meter

Phase2

Value on phase L2.

Power meter

Phase3

Value on phase L3.

Power meter

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

270.1202

Datetime Value Apparentpower 3

Date and time with apparent power on the three phases.

Parameter

Meaning

Component

Phase1

Value on phase L1.

Power meter

Phase2

Value on phase L2.

Power meter

Phase3

Value on phase L3.

Power meter

Year … SRC

Date, time and quality flag, as in DPT 19.001.

Power meter

271.1200

Tariffdayprofile

Daily tariff profile (tariff start time).

Parameter

Meaning

Component

Day

Day of the week.

Power meter

Hour

Hour 0–23.

Power meter

Minutes

Minutes 0–59.

Power meter

Seconds

Seconds 0–59.

Power meter

272.600

Converter Info

Converter information: emergency level and DALI address.

Parameter

Meaning

Component

InfoValid

Information validity.

Info

EmLevel

Emergency level.

Info

DALI_SA

DALI short address.

Info

273.001

Forecast Temperature

Temperature forecast: value, probability and lead time.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Thermostat

Probability

Forecast probability (%).

Thermostat

DelayTime

In how many minutes the change occurs.

Thermostat

273.002

Forecast Windspeed

Wind speed forecast.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Weather station

Probability

Forecast probability (%).

Weather station

DelayTime

In how many minutes the change occurs.

Weather station

273.003

Forecast Relativehumidity

Relative humidity forecast.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Climate thermostat

Probability

Forecast probability (%).

Climate thermostat

DelayTime

In how many minutes the change occurs.

Climate thermostat

273.004

Forecast Absolutehumidity

Absolute humidity forecast.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Climate thermostat

Probability

Forecast probability (%).

Climate thermostat

DelayTime

When the change occurs, in minutes.

Clima thermostat

273.005

Forecast CO2

Forecast of CO₂.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Weather station

Probability

Forecast probability (%).

Weather station

DelayTime

When the change occurs, in minutes.

Weather station

273.006

Forecast Airpollutants

Forecast of air pollutants.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Weather station

Probability

Forecast probability (%).

Weather station

DelayTime

When the change occurs, in minutes.

Weather station

273.007

Forecast Sunintensity

Forecast of solar irradiance.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Weather station

Probability

Forecast probability (%).

Weather station

DelayTime

When the change occurs, in minutes.

Weather station

274.001

Forecast Wind Direction

Forecast of wind direction.

Parameter

Meaning

Component

Mask

Which forecast fields are valid.

Weather station

Probability

Forecast probability (%).

Weather station

DelayTime

When the change occurs, in minutes.

Weather station

276.1200

ERL Status

Status of load management (duty cycles and update flags).

Parameter

Meaning

Component

DutyCycle1

Load 1 duty cycle (%).

Combo

DutyCycle2

Load 2 duty cycle (%).

Combo

DutyCycle3

Load 3 duty cycle (%).

Combo

DCA1

1 = duty cycle 1 valid.

Combo

DCA2

1 = duty cycle 2 valid.

Combo

DCA3

1 = duty cycle 3 valid.

Combo

Update

Update flag.

Combo

TA

Load management status flag.

Combo

277.1200

4 Energyregisters

Group of 4 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

278.1200

5 Energyregisters

Group of 5 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

279.1200

6 Energyregisters

Group of 6 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

280.1200

11 Energyregisters

Group of 11 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

281.1200

Datetime 4 Energyregisters

Date and time with 4 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

282.1200

Datetime 5 Energyregisters

Date and time with 5 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

283.1200

Datetime 6 Energyregisters

Date and time with 6 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter

284.1200

Datetime 11 Energyregisters

Date and time with 11 energy registers.

Parameter

Meaning

Component

EnergyRegisters

Energy registers (one per tariff or quantity).

Power meter